Installation and wiring, Rne modular controller field technical guide 40, Full digital module – Orion System RNE Modular Controller User Manual

Page 40: Zone

background image

Zone

Zone

INSTALLATION AND WIRING

RNE Modular Controller Field Technical Guide

40

AO1

AO2

+5V

SIG 2

GND

OPTI

O

N

S

ALARM

ANALOG

STAT

+5V

COMM

GND

SIG 4

GND

BIN 2

R1

R2

GND

RELAYS

ADDRESS

SIG 3

+5V

GND

BIN 1

COM

+5V

SIG 1

R3

R4

Rc

AO1

AO2

PWM1-

PWM1+

PWM2-

PWM2+

OE275-01 Suction

Pressure Transducer 2

OE370-23-FD-A

Full Digital Module

This Dip

Switch Is Not

Used For This

Application

This Dip

Switch Is Not

Used For This

Application

PWR

Connect To RNE Controller

Connect To

Head Pressure Module

HSSC Cable

24 VAC Transformer

3 VA Minimum

Line Voltage

24 V

A

C

GND

WARNING!!
Observe Polarity! All
boards must be wired
with GND-to-GND and
24 VAC-to-24 VAC.
Failure to observe
polarity could result in
damage to the boards.

HSSC Cable

NOTE:

NORMALLY OPEN AND

RATED FOR 24 VAC POWER

ALL RELAY OUTPUTS

ARE

COMPRESSOR 2 ENABLE

COMPRESSOR 1 ENABLE

R1
R2

ONLY.

1 AMP MAXIMUM LOAD.

HVAC UNIT CONNECTIONS

SIG 2

GND

+V

BK

RD
WH

SIG 1

GND

+V

BK

RD
WH

OE275-01 Suction

Pressure Transducer 1

COM

+

Compressor 2

COM

+

Compressor 1

Full Digital Module

RNE Units with DX Cooling will have either a Half VFD/Half Fixed
compressor confi guration or a Full VFD compressor confi guration. The
RNE 55 - 105 Ton units have two compressors and will have either one
VFD and one Fixed Compressor or will have two VFD Compressors.
The operation of these compressors is described in the Sequence of
Operation section of this manual.

If this is not a Water Source Heat Pump unit, the outputs to the com-
pressors will always be wired from the Full Digital Module ( OE370-
23-FD-A). Each compressor will need to have a relay confi gured and
wired from this module and the VFD output(s) will be wired from this
module. Each compressor will also have a Suction Pressure Transducer
wired into this module. See Figure 32 below for the wiring diagram.

RNE 55 - 105 Ton Unit Compressor and Condenser Wiring

The Full Digital Module connects to the RNE Controller or the Two
Condenser Head Pressure Module with an HSSC Cable. This allows
setpoints, status values, and alarms to be communicated between the
RNE Controller and the Full Digital Module. This module requires a
24 VAC power connection with an appropriate VA rating.

NOTE: The Compressor Relays on the Full Digital Module are

used rather than the relay outputs on the RNE Control-
ler.

NOTE: For more information, see the Full Digital Module

Technical Guide on our website orioncontrols.com.

Figure 32: RNE 55 - 105 Ton Unit Two Compressor Full Digital Wiring