beautypg.com

Rne controller troubleshooting, Rne modular controller field technical guide 74, Oe271 pressure sensor testing – Orion System RNE Modular Controller User Manual

Page 74

background image

Zone

Zone

RNE CONTROLLER TROUBLESHOOTING

RNE Modular Controller Field Technical Guide

74

OE271 Pressure Sensor Testing Instructions

Use the voltage column to check the Duct Static Pressure Sensor while
connected to powered controllers. Read voltage with meter set on DC
volts. Place the “-” (minus) lead on the GND terminal and the “+” (plus)
lead on the 0-5 pin terminal on (TP) with the jumper removed. Be sure
to replace the jumper after checking.

OE258-01 Building Pressure Sensor Testing

Instructions

Use the voltage column to check the Building Static Pressure Sensor
while connected to a powered expansion module. Read voltage with
meter set on DC volts. Place the “-” (minus) lead on terminal labeled
GND and the “+” lead on terminal AIN4 on the Analog Input/Output
Expansion Module.

OE271 & OE258-01 Pressure Sensor Testing

OE271 Pressure Sensor Testing

The table below is used to troubleshoot the OE271 Duct Static Pressure
Sensors.

OE258-01 Pressure Sensor Testing

The table below is used to troubleshoot the OE258-01 Building Pres-
sure Sensors.

OE271 Duct Static Pressure Sensor

Pressure

@

Sensor

(“ W.C.)

Voltage

@

Input

(VDC)

Pressure

@

Sensor

(“ W.C.)

Voltage

@

Input

(VDC)

0.00

0.25

2.60

2.33

0.10

0.33

2.70

2.41

0.20

0.41

2.80

2.49

0.30

0.49

2.90

2.57

0.40

0.57

3.00

2.65

0.50

0.65

3.10

2.73

0.60

0.73

3.20

2.81

0.70

0.81

3.30

2.89

0.80

0.89

3.40

2.97

0.90

0.97

3.50

3.05

1.00

1.05

3.60

3.13

1.10

1.13

3.70

3.21

1.20

1.21

3.80

3.29

1.30

1.29

3.90

3.37

1.40

1.37

4.00

3.45

1.50

1.45

4.10

3.53

1.60

1.53

4.20

3.61

1.70

1.61

4.30

3.69

1.80

1.69

4.40

3.77

1.90

1.77

4.50

3.85

2.00

1.85

4.60

3.93

2.10

1.93

4.70

4.01

2.20

2.01

4.80

4.09

2.30

2.09

4.90

4.17

2.40

2.17

5.00

4.25

2.50

2.25

OE258-01 Building Pressure Sensor

Pressure

@

Sensor

(“ W.C.)

Voltage

@

Input

(VDC)

Pressure

@

Sensor

(“ W.C.)

Voltage

@

Input

(VDC)

-0.25

0.00

0.01

2.60

-0.24

0.10

0.02

2.70

-0.23

0.20

0.03

2.80

-0.22

0.30

0.04

2.90

-0.21

0.40

0.05

3.00

-0.20

0.50

0.06

3.10

-0.19

0.60

0.07

3.20

-0.18

0.70

0.08

3.30

-0.17

0.80

0.09

3.40

-0.16

0.90

0.10

3.50

-0.15

1.00

0.11

3.60

-0.14

1.10

0.12

3.70

-0.13

1.20

0.13

3.80

-0.12

1.30

0.14

3.90

-0.11

1.40

0.15

4.00

-0.10

1.50

0.16

4.10

-0.09

1.60

0.17

4.20

-0.08

1.70

0.18

4.30

-0.07

1.80

0.19

4.40

-0.06

1.90

0.20

4.50

-0.05

2.00

0.21

4.60

-0.04

2.10

0.22

4.70

-0.03

2.20

0.23

4.80

-0.02

2.30

0.24

4.90

-0.01

2.40

0.25

5.00

0.00

2.50

Table 6: Duct Static Pressure/Voltage for