Rne controller troubleshooting, Rne modular controller field technical guide 74, Oe271 pressure sensor testing – Orion System RNE Modular Controller User Manual
Page 74
Zone
Zone
RNE CONTROLLER TROUBLESHOOTING
RNE Modular Controller Field Technical Guide
74
OE271 Pressure Sensor Testing Instructions
Use the voltage column to check the Duct Static Pressure Sensor while
connected to powered controllers. Read voltage with meter set on DC
volts. Place the “-” (minus) lead on the GND terminal and the “+” (plus)
lead on the 0-5 pin terminal on (TP) with the jumper removed. Be sure
to replace the jumper after checking.
OE258-01 Building Pressure Sensor Testing
Instructions
Use the voltage column to check the Building Static Pressure Sensor
while connected to a powered expansion module. Read voltage with
meter set on DC volts. Place the “-” (minus) lead on terminal labeled
GND and the “+” lead on terminal AIN4 on the Analog Input/Output
Expansion Module.
OE271 & OE258-01 Pressure Sensor Testing
OE271 Pressure Sensor Testing
The table below is used to troubleshoot the OE271 Duct Static Pressure
Sensors.
OE258-01 Pressure Sensor Testing
The table below is used to troubleshoot the OE258-01 Building Pres-
sure Sensors.
OE271 Duct Static Pressure Sensor
Pressure
@
Sensor
(“ W.C.)
Voltage
@
Input
(VDC)
Pressure
@
Sensor
(“ W.C.)
Voltage
@
Input
(VDC)
0.00
0.25
2.60
2.33
0.10
0.33
2.70
2.41
0.20
0.41
2.80
2.49
0.30
0.49
2.90
2.57
0.40
0.57
3.00
2.65
0.50
0.65
3.10
2.73
0.60
0.73
3.20
2.81
0.70
0.81
3.30
2.89
0.80
0.89
3.40
2.97
0.90
0.97
3.50
3.05
1.00
1.05
3.60
3.13
1.10
1.13
3.70
3.21
1.20
1.21
3.80
3.29
1.30
1.29
3.90
3.37
1.40
1.37
4.00
3.45
1.50
1.45
4.10
3.53
1.60
1.53
4.20
3.61
1.70
1.61
4.30
3.69
1.80
1.69
4.40
3.77
1.90
1.77
4.50
3.85
2.00
1.85
4.60
3.93
2.10
1.93
4.70
4.01
2.20
2.01
4.80
4.09
2.30
2.09
4.90
4.17
2.40
2.17
5.00
4.25
2.50
2.25
OE258-01 Building Pressure Sensor
Pressure
@
Sensor
(“ W.C.)
Voltage
@
Input
(VDC)
Pressure
@
Sensor
(“ W.C.)
Voltage
@
Input
(VDC)
-0.25
0.00
0.01
2.60
-0.24
0.10
0.02
2.70
-0.23
0.20
0.03
2.80
-0.22
0.30
0.04
2.90
-0.21
0.40
0.05
3.00
-0.20
0.50
0.06
3.10
-0.19
0.60
0.07
3.20
-0.18
0.70
0.08
3.30
-0.17
0.80
0.09
3.40
-0.16
0.90
0.10
3.50
-0.15
1.00
0.11
3.60
-0.14
1.10
0.12
3.70
-0.13
1.20
0.13
3.80
-0.12
1.30
0.14
3.90
-0.11
1.40
0.15
4.00
-0.10
1.50
0.16
4.10
-0.09
1.60
0.17
4.20
-0.08
1.70
0.18
4.30
-0.07
1.80
0.19
4.40
-0.06
1.90
0.20
4.50
-0.05
2.00
0.21
4.60
-0.04
2.10
0.22
4.70
-0.03
2.20
0.23
4.80
-0.02
2.30
0.24
4.90
-0.01
2.40
0.25
5.00
0.00
2.50
Table 6: Duct Static Pressure/Voltage for
OE271 Duct Static Pressure Sensors
Table 7: Building Static Pressure/Voltage for
OE258-01 Building Pressure Sensors