RNE Modular Controller Field Technical Guide

INSTALLATION AND WIRING

23

OAT Sensor Wiring

Outdoor Air

Temperature Sensor

AI4

GND

Make Splice Connections

Inside Sensor Enclosure

As Shown. Seal All Conduit

Fittings With Silicone

Sealant

Mount Sensor Outdoors

In Shaded Protected

Area & In Upright

Position As Shown

Be Sure Jumper Is Set

For THERM

On AI4 For Outdoor

Air Temperature Sensor

AI1

AI1 SET

AI2 SET

AI3 SET

AI4 SET

AI5 SET

AI7 SET

AI2

AI3

AI4

AI5

AI7

RNE Controller

Outdoor Air Temperature Sensor

The OE250 Outdoor Air Temperature Sensor must be wired as shown
in Figure 13 below for proper operation of the RNE Controller. The
Outdoor Air Temperature Sensor is a 10K Type III thermistor sensor.
The sensor should be mounted in the upright position as shown in an
area that is protected from the elements and direct sunlight. Be sure to
make the wiring splices inside of the Outdoor Air Temperature Sensor
weather-tight enclosure.

Figure 13: OE250 – Outdoor Air Temperature Sensor Wiring

CAUTION: Be sure to mount the Outdoor Air Temperature
Sensor in an area that is not exposed to direct sunlight. The shaded
area under the HVAC unit rain hood is normally a good location.
Unused conduit opening(s) must have closure plugs installed and
must be coated with sealing compound to provide a rain-tight seal.
Water can damage the sensor.