Installation and wiring, Rne modular controller field technical guide, Figure 16: zoning bypass damper actuator wiring – Orion System RNE Modular Controller User Manual
Page 25: Figure 15: supply fan vfd wiring

RNE Modular Controller Field Technical Guide
INSTALLATION AND WIRING
25
Supply Fan VFD Signal or Zoning
Bypass Damper Actuator Signal
The Supply Fan VFD or Zoning Bypass Damper Actuator Signal is a
0-10 VDC output. This signal output can be connected to the Supply
Fan Variable Frequency Drive to modulate the Supply Fan speed and
control Duct Static Pressure utilizing the Duct Static Pressure Sensor
connected to the RNE Controller. Alternatively, it can be connected to a
Zoning Bypass Damper Actuator that will modulate the Zoning Bypass
Damper Actuator to control Duct Static Pressure utilizing the Duct Static
Pressure Sensor connected to the RNE Controller. A Duct Static Pressure
Sensor must be connected in order for the VFD or Zoning Bypass Damper
Actuator to operate. See Figures 15 and 16 below for detailed wiring.
Supply Fan VFD Signal and Zoning Bypass Damper Actuator
CAUTION: Variable Frequency Drive units can cause large
transient noise spikes which can cause interference to be propagated
on other electronic equipment. Use shielded wire wherever possible
and route all sensor and controller wiring away from the Variable
Frequency Drive and the HVAC Unit electrical wiring.
Figure 16: Zoning Bypass Damper Actuator Wiring
+
Supply Fan Variable Frequency Drive
(By Others)
_
0-10VDC Input From AO2
Shield
GND
Caution:
The VFD Unit Must Be Configured For 0-10 VDC Input.
The Input Resistance At The VFD Must Not Be Less
Than 1000 Ohms When Measured At The VFD
Terminals With All Input Wires Removed.
Note:
Wire To The VFD Using 18 GA Minimum 2
Conducter Twisted Pair With Shield Cable.
Wire Shield To GND As Shown
AO2
GND
Shield
RNE Controller
AI1
AI1 SET
AI2 SET
AI3 SET
AI4 SET
AI5 SET
AI7 SET
AI2
AI3
AI4
AI5
AI7
Bypass Damper Actuator
(Belimo Actuator Shown)
0-10 VDC
24 VAC Power Source
Sized For Actuator VA Load
GND
24 VAC
3 (Y)
5 (U)
2 (+)
1 (-)
Belimo Actuator Wiring Shown.
Consult Factory For Other
Manufacturer Wiring Instructions.
RNE Controller
GND
AO2
AI1
AI1 SET
AI2 SET
AI3 SET
AI4 SET
AI5 SET
AI7 SET
AI2
AI3
AI4
AI5
AI7
Figure 15: Supply Fan VFD Wiring