3 evaporator fan assembly, 4 condenser fan assembly, 5 wiring notice – MovinCool CM12 Service Manual User Manual
Page 72: 6 perform an inspection

Repair Section
72
4) Braze pipe at point A and G, then braze at point
B.
< NOTE >
Pipe is packaged in the supplied compressor
assembly.
5) Re-install overload relay, wires, and plastic cover
after brazing.
6) Apply insulators to the accumulator and pipe 2.
< NOTE >
Insulators are packaged in the supplied
compressor assembly.
10.3 Evaporator Fan Assembly
• Install evaporator fan. Allow a clearance of 0.12 in (3.0 mm) or more on each side of the
evaporator fan. (See page 52.)
10.4 Condenser Fan Assembly
• Install condenser fan. Allow a clearance of 0.12 in (3.0 mm) or more on each side of the
condenser fan. (See page 54.)
10.5 Wiring Notice
• Secure the wires using clamps so that they do not come into contact with the edges of the
structure. Secure the wires using clamps in the same position they were before removal.
10.6 Perform an Inspection
• Perform an inspection of cooling performance and check for abnormal noise or vibration.
ILL00626-00
Pipe
A
G
B
ILL00627-00
Accumulator
Insulators