Repair Section

45

7.7 Inspection of Fan Motor

(1) Evaporator fan motor

• Measure resistance across the terminals of the fan motor.
• Between terminals (at 77 °F (25 °C))

- Black-White Approx. 24.5 ohm
- Black-Blue Approx. 36.5 ohm
- Black-Red Approx. 39.0 ohm

• If the measured resistance is not equal to the standard values listed above, replace the fan

motor.

(2) Condenser fan motor

• Measure resistance across the terminals of the

fan motor.

• Between terminals (at 77 °F (25 °C))

- Black-White Approx. 8.8 ohm
- Black-Blue Approx. 7.0 ohm
- Black-Red Approx. 18.6 ohm

• If the measured resistance is not equal to the

standard values listed above, replace the fan
motor.

7.8 Inspection of Thermistor

• Using an Ohm-meter, check the resistance value across the 2-pin connector. At normal

temperature (77 °F (25 °C)) all thermistors (evaporator inlet air, freeze protection, or condenser
inlet air) should measure approximately 5 k ohm.

• Thermistors:

- Evaporator inlet air thermistor (RTS)
- Condenser inlet air thermistor (ODS)
- Freeze protection thermistor (CTS)