6.2 Millivolt Wall Thermostat Connection

1) Use with a single stage wall thermostat.

Thermostat type: Millivolt System

2) Set the wall thermostat to cooling system mode, since most wall thermostats are designed for

both heating and cooling.

3) Prepare the wire harness for connection from the unit to the thermostat. The recommended wire size is:

Wire Type: Thermostat cable / Solid wire 16 ~ 26 AWG

4) Identify the thermostat connectors labeled G, G1, Y, and RC.

G (Fan On/Off), G1 (Fan Speed Hi/Lo), Y (Cooling On/Off) and RC (Cooling Transfer - Common)

Connecting Thermostat to CM 12 Unit

< NOTE >

Use thermostat that is compatible with millivolt system. Do not connect thermostat to AC power source.

Wall Thermostat

Connector Name

CM 12 WIRES

Function

Label Name

Color

RC

RC

Brown

Common line for thermostat connection.

Y

Y

Red

When both Y and G signals are ON, the compressor comes ON.

G

G

Orange

When the G signal is ON, the evaporator fan comes ON.
(When the signal is OFF, the evaporator fan goes OFF.)

G1

G1

Yellow

When the G1 signal is ON, the evaporator fan speed switches to Lo.
(When the signal is OFF, the evaporator fan speed switches to Hi.)

ILL00615-00

CM 12 Unit

Thermostat

(Millivolt System)

Orange Wire

G

Y

RC

G1

Red Wire

GY

W

R

C
R

H
O

B

Brown Wire

Yellow Wire

Remove Factory-Installed Jumper

Use only with thermostat that has
Fan Hi-Lo Speed control.