26 (2) dip switch setting – MovinCool CM12 Service Manual User Manual
Page 26

Operation Section
26
(2) Dip switch setting
• The controller is equipped with a four position dip switch that defaults in the OFF position. The
dip switch can be set to configure the following functions:
Switch
Setting Name
Function
DSW4
Alarm Setting
When DSW 4 is ON, the buzzer sound function is disabled.
DSW3
Compressor Time Delay Cut
When DSW 3 is ON, the compressor delay timer function is disabled.
DSW2
Cooling Test Operation
When DSW 2 is ON, the compressor, evaporator and condenser fan
motor will turn ON. This function is used for test purposes and verification.
DSW1
Discharge Air Test Operation
When DSW 1 is ON, the evaporator and condenser fan motor will turn
ON. This function is used for test purposes and verification.
I002759
1
2
ON
3
4
4-Position Dipswitch
"OFF" Position
Relay Board Fuse (5A)