(2) Dip switch setting

• The controller is equipped with a four position dip switch that defaults in the OFF position. The

dip switch can be set to configure the following functions:

Switch

Setting Name

Function

DSW4

Alarm Setting

When DSW 4 is ON, the buzzer sound function is disabled.

DSW3

Compressor Time Delay Cut

When DSW 3 is ON, the compressor delay timer function is disabled.

DSW2

Cooling Test Operation

When DSW 2 is ON, the compressor, evaporator and condenser fan
motor will turn ON. This function is used for test purposes and verification.

DSW1

Discharge Air Test Operation

When DSW 1 is ON, the evaporator and condenser fan motor will turn
ON. This function is used for test purposes and verification.

I002759

1

2

ON

3

4

4-Position Dipswitch

"OFF" Position

Relay Board Fuse (5A)