MovinCool CM12 Service Manual User Manual
Page 40

Repair Section
40
< NOTE >
*1 :To RESET, reset power source or turn the wall thermostat off and on.
Unit does
not operate.
2
Drain hose
Drain hose clogged
(for internal drain pump).
Remove any blockage or excessive
kinks preventing water flow.
RESET
*1
.
Drain hose trap position is too
high to pump up condensation
water (for internal drain pump).
Improve hose installation.
(Refer to the operation manual of this
unit.)
RESET
*1
.
Internal drain pump
Internal drain pump is not
working.
Reconnect the internal drain pump
and check connection.
RESET
*1
.
If the internal drain pump still does
not work, replace it.
3
Refrigeration system
Refrigeration system problem.
Check for leakage.
Check compressor relay.
Check for refrigerant blockage.
RESET
*1
.
4
Fire alarm system
Signal is input from the fire
alarm.
Check the fire alarm system and
confirm there is no signal input to the
unit, then RESET
*1
.
Condition
Alarm
Pattern
Check Area
Possible Cause
Remedy