Repair Section

40

< NOTE >

*1 :To RESET, reset power source or turn the wall thermostat off and on.

Unit does
not operate.

2

Drain hose

Drain hose clogged
(for internal drain pump).

Remove any blockage or excessive
kinks preventing water flow.
RESET

*1

.

Drain hose trap position is too
high to pump up condensation
water (for internal drain pump).

Improve hose installation.
(Refer to the operation manual of this
unit.)
RESET

*1

.

Internal drain pump

Internal drain pump is not
working.

Reconnect the internal drain pump
and check connection.
RESET

*1

.

If the internal drain pump still does
not work, replace it.

3

Refrigeration system

Refrigeration system problem.

Check for leakage.
Check compressor relay.
Check for refrigerant blockage.
RESET

*1

.

4

Fire alarm system

Signal is input from the fire
alarm.

Check the fire alarm system and
confirm there is no signal input to the
unit, then RESET

*1

.

Condition

Alarm

Pattern

Check Area

Possible Cause

Remedy