Repair Section

44

7.6 Inspection of Compressor

(1) Compressor motor

• Measure resistance across the terminals of the

compressor motor.

• Between terminals (at 77 °F (25 °C))

- R-C Approx. 0.49 - 0.8 ohm
- C-S Approx. 1.9 - 3.3 ohm

• If the measured resistance is not equal to the

standard values listed above, replace the
compressor. The compressor has an external overload relay. The overload relay should be
operational if the above resistance is obtained under normal temperature. For overload relay
specifications, see chart on page 27.

(2) Overload relay

• Check for continuity across two terminals of the

overload relay. At normal temperature, there
should be continuity across the terminals.

• If there is no continuity across the terminals,

replace the overload relay.

Operating Temperature

OFF (open contacts)

ON (closed contacts)

302 °F (150 °C)

142 °F (61 °C)

I002770

C

R

S

I001701