beautypg.com

7 capacitor, 8 temperature thermistor, 9 drain pump – MovinCool CM12 Service Manual User Manual

Page 29: Capacitor, Temperature thermistor, Drain pump

background image

Operation Section

29

5.7 Capacitor

• The capacitor is used to improve the rotational

power of the fan motors and compressor at
startup. The specification for each capacitor is
shown below.

5.8 Temperature Thermistor

• The evaporator inlet air thermistor (RTS) is

installed upstream of the evaporator, and
detects evaporator inlet temperature as a
resistance value.

• The freeze protection thermistor (CTS) is

installed in the evaporator outlet piping, and
detects low temperature on the evaporator as
a resistance value.

5.9 Drain Pump

• The drain pump evacuates evaporator

condensation accumulated in the drain pan.
The drain pump turns on when the compressor
turns on. The drain pump turns off when the
compressor turns off.

Capacitor

Rated

Voltage

Capacitance

Evaporator Fan Motor

250 V

7 µF

Condenser Fan Motor

220 V

9 µF

Compressor

370 V

60 µF

Type

Specification

Characteristic

“Short” Detection

“Open” Detection

Evaporator Inlet
Air Thermistor (RTS)

5 k ohm at 77 °F (25 °C)

181 °F (83 °C) or more

-29 °F (-34 °C) or less

Freeze Protection
Thermistor (CTS)

5 k ohm at 77 °F (25 °C)

181 °F (83 °C) or more

-29 °F (-34 °C) or less

ILL00561-00

I001695

I000523