Repair Section

61

9.2 Removal of Refrigeration System Components

WARNING

• Before replacing any refrigeration component, recover the refrigerant using standard

recovery procedures and equipment.

• When recovering the refrigerant, use the pinch-off tube as shown in figure below.

CAUTION

• To prevent oxidation, dry nitrogen should be conducted (flow rate 0.27 gal/min (1 L/min)) through

the pinch-off tube during any brazing operation.

• During any component replacement involving brazing, to protect them from the flame, shield

nearby parts with a steel plate, etc.,

• Evaporator
• Capillary tube
• Condenser
• Compressor
• High pressure switch

ILL00547-01

Part to Replace
• Compressor
• Condenser
• Capillary Tube

• High Pressure Switch

Disconnect at

F

• Evaporator

B & C

A & C

C, D & E

See page 62.

B

G

F

A

C

A

E

D

Tube

Pipe