Specifications, 1 technical specifications, Technical specifications – MovinCool CM12 Service Manual User Manual
Page 11

Operation Section
11
3. SPECIFICATIONS
3.1 Technical Specifications
ITEM
SPECIFICATIONS
Electronic Features
Control
Millivolt Thermostat (Field supplied)
Electrical Characteristics
Voltage Requirement
Single-Phase, 115 V, 60 Hz
Operating Voltage
Range
Max.
127 V
Min.
104 V
Starting Current
50 A
Recommended Fuse Size
15 A
FLA
11.2 A
MCA
14.9 A
MOP
20 A
LRA
50 A
Cooling Capacity and Power Consumption
Evaporator: 80°F (27°C),
50% RH
Condenser: 95°F (35°C),
50% RH
Total Cooling Capacity
*1
10500 Btu/h (3090 W)
Sensible Cooling Capacity
*1
7200 Btu/h (2100 W)
Power Consumption
*1
1.23 kW
Current Consumption
*1
11.2 A
EER
8.5
Power Factor
96%
Evaporator: 72°F (22°C),
50% RH
Condenser: 95°F (35°C),
50% RH
Total Cooling Capacity
*1
9300 Btu/h (2730 W)
Sensible Cooling Capacity
*1
7000 Btu/h (2040 W)
Power Consumption
*1
1.22 kW
Current Consumption
*1
11.1 A
EER
7.6
Power Factor
96%
Compressor
Type
Hermetic Rotary
Output
0.91 kW
Evaporator
Type of Evaporator
Plate Fin
Type of Fan
Centrifugal Fan
Air Flow
High
324 CFM (550 m
3
/h)
Low
228 CFM (390 m
3
/h)
Max. External Static Pressure
0.16 IWG (40 Pa)
Motor Output
High
0.04 kW
Low
0.01 kW