Baud rate bn – Measurement Computing Serial488/4 User Manual
Page 42

Section 3
Command Descriptions
3.3
Baud Rate
Bn
The Baud Rate command programs the speed at which serial data is
transmitted and received by the selected serial port. The Port Select command (Pn)
is used to select the serial port regardless of addressing mode in use. Additionally the
CTS
line may be used to input a clock signal which is sixteen times the desired baud
rate if B11 is selected. The factory default setting as set by the Save Configuration
command (S0) is B9, 9600 baud.
NOTE: The sum of the baud rates for all four ports cannot exceed 38,400 baud or data
may be lost.
B0
110 baud selected
B1
300 baud selected
B2
600 baud selected
B3
1200 baud selected
B4
1800 baud selected
B5
2400 baud selected
B6
3600 baud selected
B7
4800 baud selected
B8
7200 baud selected
B9
9600 baud selected
B10
19200 baud selected
B11
16 x External clock selected
B?
Return current baud setting
Example1: Set baud rates for ports 1 and 2 using dual primary addressing mode
PRINT#1,"CLEAR08"
reset the Serial488/4
PRINT#1,"OUTPUT08;P1X"
select port 1 as the current port
PRINT#1,"OUTPUT08;B3X"
select 1200 baud
PRINT#1,"OUTPUT08;P2B10X"
select 19200 baud on port 2
Example 2: Set baud rates for ports 1 and 2 using secondary addressing mode
PRINT#1,"CLEAR0800"
reset the Serial488/4
PRINT#1,"OUTPUT0800;P1B3X"
select 1200 baud for port 1
PRINT#1,"OUTPUT0800;P3b10X"
select 19200 baud for port 3