beautypg.com

Legrand RW600B User Manual

Sensor de desocupación, Rw600b vacancy sensor switch, Rw600b

background image

2. Identify the type of circuit.

In a Single Pole Circuit (see Fig. 2), two single wires

connect to two screws on the existing switch. A ground

wire may also be present and connected to a ground

terminal on the old switch.

CAUTION

For your safety: Connecting a proper ground to the

sensor provides protection against electrical shock

in the event of certain fault conditions. If a proper

ground is not available, consult with a qualified

electrician before continuing installation.

Only connect the RW600B to a Single Pole Circuit. The

RW600B is not suitable for 3-way switching. If the existing wiring does not match the

description for a Single Pole Circuit, you should consult with a qualified electrician.

3. Prepare the Wires.

Tag the wires currently connected to the existing switch, so

that they can be identified later. Disconnect the wires. Make

sure the insulation is stripped off the wires to expose their

copper cores to the length indicated by

the “Strip Gage,” in Fig. 3 (approximately 1/2 inch).

4. Wire the sensor.

Twist the existing wires together

with the wire leads on the RW600B

sensor as indicated below. Cap

them securely using the wire nuts

provided. See Fig 4.

• Connect the green or non-insulated

(copper) GROUND wire from the

circuit to the green ground wire on

the RW600B. Make sure there is a

solid ground connection.

• Connect the power wire from the

circuit (HOT) to the black wire on

the RW600B.

• Connect the power wire to the lamp

or fan (LOAD) to the red wire on the

RW600B.

5. Put the RW600B in the wall box.

Position the lens above the ON/OFF button (lens at top, button at bottom). Secure it

to the wall box with the screws provided.

6. Make any necessary adjustments.

See the SENSOR ADJUSTMENT section for

information.

7. Attach the new cover plate.
8. Restore power to the circuit.

Turn on the breaker or replace the fuse.

INITIAL POWER UP DELAY

There is an initial warm-up and calibration period the first time power is applied to the

unit after a power failure lasting more than 5 minutes, and after the load is replaced.

SENSOR ADJUSTMENT & PROGRAMMING

To adjust the RW600B, use controls located under the front

cover (lens and ON/OFF button). The wall switch wallplate

must be removed to gain access to the adjustment dial

under the ON/OFF button.
1. Remove the wallplate.
2. Firmly grasp the edges of the front cover

directly below the lens where it says “open”

(see Fig. 5). Push in one side first until it

pops out, then the other side. Remove front

cover from the unit.

Adjusting the Time Delay

The factory setting for the time delay dial is fully clockwise,

providing the maximum delay of 30 minutes. To reduce the

amount of time the load remains ON after the last motion

detection, turn the dial counterclockwise (minimum = 30

seconds). You can set the following times: 30 minutes, 20

minutes, 10 minutes, 5 minutes, 30 seconds.

CAUTION

Do not overturn the time delay adjustment dial.

Status LED

The small slide switch located to the right of the dial (see Fig.

6) enables and disables the Status LED indicator light on the

ON/OFF button. The factory default setting is enabled. When

enabled the Status LED blinks when the sensor detects motion, whether the load is ON

or OFF. To disable the blinking LED, move the slide switch to the right toward “OFF.”

CHANGING THE COLOR OF THE UNIT

1. Remove the wallplate
2. Firmly grasp the edges of the front cover directly below

the lens where it says “open.” Push in one side first

until it pops out, then the other side. Remove

front cover from the unit (see Fig. 5).

3. Take the new color front cover, place the top

peg in first then snap in each side one at a

time (see Fig. 7).

TROUBLESHOOTING

Status LED is enabled but not blinking and the load will not turn ON:

• Check the circuit breaker to be sure it is functioning.

Load will not turn ON:

Press ON/OFF button. The load should turn ON. If not:
• Check the light bulb and/or motor switch on the fan mechanism.
• Turn off power to the circuit then check wire connections.

Load will not turn OFF:

Note: The time delay can be set from 30 seconds to 30 minutes. Ensure that the time

delay is set to the desired delay and that there is no movement within the sensor’s view

for that time period.
• To quickly test the unit for proper operation, turn the time delay to minimum and

move out of the sensor’s view. Lights should turn off after 30 seconds.

• Press the ON/OFF button. If load does not turn off, turn off power to the circuit then

check wire connections.

• If load still does not turn off call 800.223.4185 for technical support

Green -> GROUND

Black -> HOT (power

from circuit box)

Time

Delay

Motion Blin

k

OFF

30sec.

30mi

n.

5min.

10m

in.

20m

in.

11543r

1

Red -> LOAD (power

to lamp or fan)

OPEN

Fig 4: Sensor orientation, wire connections

and wall box assembly

Ground

HOT (power from

circuit box)

LOAD

(power

to lamp)

NEUTRAL

Fig 2: Typical Single Pole

Switch Wiring

Strip Gage

1/2"

12.7mm

Fig 3: Wire Stripping

DESCRIPTION AND OPERATION

The RW600B Vacancy Sensor is designed to replace a standard light or fan switch. The

sensor uses passive infrared technology to sense human motion in a space and turn the

light OFF when the room is vacant. It is ideal for applications in a home where there is

a direct line of sight from the sensor to the room including bedrooms and family/living

rooms.
Like a standard switch, pressing the ON/OFF button will turn the light or fan (controlled

load) ON and OFF. Unlike a standard switch, the RW600B automatically turns OFF the

controlled load after the coverage area has been vacant for a period of time known as

the Time Delay. If motion is detected within 30 seconds after it automatically turns OFF,

the RW600B automatically turns the load back ON.

Indicator Light

The Status LED located on the ON/OFF button blinks

upon initial detection. It will blink again when it

detects a change of infrared energy in the space.

The LED can be disabled. See Status LED.

Coverage Area

The RW600B has a maximum coverage range of

180 degrees and a coverage area of 600 square feet

(56 square meters). The sensor must have a clear

and unobstructed view of the coverage area. Objects

blocking the sensor’s lens may prevent detection

thereby causing the light to turn off even though

someone is in the area.

Windows, glass doors, and other transparent

barriers will obstruct the sensor’s view

and prevent detection.

INSTALLATION & WIRING

1. Prepare the switch box.

After the power is turned off at the circuit breaker box, remove the existing wall plate

and mounting screws. Pull the old switch out from the wall box.

25'

(7.6m)

12'

(3.7m)

Fig 1: Sensor Coverage Area

WARNING

Disconnect power to the wall switch box by turning OFF

the circuit breaker or removing the fuse for the circuit before installing

the RW600B, replacing lamps, or doing any electrical work.

www.legrand.us.com

Call 800.223.4185 for Technical Support

Time

Dela

y

Motion

Blink

OFF

30sec.

30min

.

5min.

10min

.

20min

.

11543r

1

Fig 5: Remove Front Cover

Time
Delay
Dial

Time
Delay

Status LED
OFF

11543r1

Status
LED
Switch

OPEN

OPEN

30sec.

30min.

Fig 6: Location of

Adjustments

Time

Dela

y

Motion

Blink

OFF

30sec.

30min

.

5min.

10min

.

20min

.

11543r

1

Fig 7: Replace Front Cover

RW600B

Vacancy Sensor Switch

Lens

ON/OFF button with

LED for motion

detection

In

sta

lla

tio

n I

ns

tru

cti

on

s

Please read all instructions before installing

SPECIFICATIONS

Voltage .................................................................................120VAC, 60Hz

Load (Single Pole Circuit)

Incandescent or fluorescent light ........................................ 0-600 Watt

Fan motor .................................................................................... 1/6 hp

Time Delay ......................................................... 30 seconds to 30 minutes

Environment .....................................................Residential Indoor use only

Operating Temperature .................................. 32° to 131°F (0° to 55°C)

Humidity .........................................................95% RH, non-condensing

Tools Needed

Insulated Screwdriver

Wire Strippers

Please

Recycle

P.O. Box 4822, Syracuse, NY 13221-4822

Technical Support: 800.223.4185

www.legrand.us

Made in China. Part No. 340904

WARRANTY INFORMATION

Pass & Seymour/Legrand warranties its products to be free of defects in materials

and workmanship for a period of five (5) years. There are no obligations or liabilities

on the part of Pass & Seymour/Legrand for consequential damages arising out of, or

in connection with, the use or performance of this product or other indirect damages

with respect to loss of property, revenue or profit, or cost of removal, installation or

reinstallation.

DESCRIPCION Y OPERACION

El sensor de desocupación RW600B sustituye un interruptor de luz convencional o

el interruptor de un ventilador. El sensor utiliza la tecnologia InfraRojo pasivo que

detecta movimento dentro del espacio, y procede a apagar la luz o el ventilador cuando

el espacio no esta ocupado. Es ideal para aplicaciones en el hogar, por ejemplo en

recamaras o en salas de estancia, donde hay una linea directa entre el objeto y el

sensor.
Igual que con un interruptor convencional, usted presiona el botón de ENCENDIDO/

APAGADO para encender o apagar la luz o ventilador (carga controlada). Sin embargo,

el RW600B apagará automáticamente la carga controlada cuando el área de cobertura

ha permanecido desocupada por un período de tiempo definido como Retardo de

Apagado. Si se detecta movimiento durante los siguientes 30 segundos después de

que la carga se ha apagado automáticamente, el RW600B la encenderá nuevamente en

forma también automática.

Luz Indicadora

Esta luz es el LED ubicado en el boton ON/OFF. La luz parpadea cuando detecta

inicialmente y cuando hay un cambio de energia

InfraRoja dentro del espacio. Se puede inactivar esta

luz. Ver la seccion de LUZ INDICADORA.

Area de Cobertura

El RW600B tiene un campo de cobertura máximo de

180 grados, y cubre un área de 600 pies cuadrados

(56 metros cuadrados). Para funcionar correctamente,

el RW600B require tener visibilidad sin obstruccion

algina entre el sensor y los objetos dentro del espacio.

Cualquier cosa que bloquea el lente puede causar

mal funcionamiento, incluyendo el apagar la luz

aunque haya persona dentro del espacio.

Ventanas, puertas de vidrio, y otras barreras

transparentes obstruirán la cobertura

del sensor y evitarán que haya detección.

25'

(7.6m)

12'

(3.7m)

Fig 1: Patrón de cobertura del

sensor

www.legrand.us.com

RW600B

Sensor de Desocupación

Lente

Botón de

ENCENDIDO/

APAGADO con

Luz Indicador

In

sta

lla

tio

n I

ns

tru

cti

on

s

Por favor leer todas las instrucciones antes de realizar la instalación

ESPECIFICACIONES

Voltaje ..................................................................................120VAC, 60Hz

Carga (Circuito unipolar)

Lámparas incandescentes o fluorescentes .........................0-600 Watts

Motor de ventila ............................................................................. 1/6hp

Retardo de Apagado ..........................desde 30 segundos hasta 30 minutos

Condiciones de operación .............. Solo para uso residencial en interiores

Temperatura ..............................................entre 32° y 131°F (0° y 55°C)

Humedad ...............................95% humedad relativa, sin condensación

Herramientas necesarias

Desatornillador con aislamiento

Peladora de cable

INSTALACION Y CABLEADO

1. Prepare la caja de conexiones.

Después de haber desconectado la corriente eléctrica a

nivel del disyuntor (breaker) del circuito correspondiente,

retire la placa del interruptor y los tornillos de montaje.

Extraiga el interruptor existente

de la caja.

2. Identifique el tipo de circuito.

En un Circuito Unipolar (ver Fig. 2), dos cables

independientes se conectan a dos tornillos en el

interruptor existente. Un cable de conexión a tierra

también puede estar presente en la caja de conexiones y

conectado a la terminal de tierra del interruptor.

PRECAUCION

Por su propia seguridad: el conectar el sensor apropiadamente a tierra

provee protección contra un choque eléctrico que pueda ocurrir en caso de

una operación defectuosa. Si no hay disponibilidad de una conexión a tierra,

consulte con un electricista calificado antes de continuar con la instalación.

Conecte el RW600B únicamente a un Circuito Unipolar. El RW600B no está

diseñado para operar en una configuración tipo “3 vías” (3-way). Si el cableado

existente en la caja de conexiones no concuerda con la descripción de un Circuito

Unipolar, usted debe consultar con un electricista calificado.

3. Prepare los cables.

Ponga algún identificador en cada uno de los cables

actualmente existentes en la caja de conexiones de

tal forma que pueda identificarlos posteriormente.

Desconecte los cables. Asegúrese de que el aislante del

cable se encuentra pelado apropiadamente para exponer

el interior de alambre de cobre a un largo de aproximadamente 1/2 pulgada y de

acuerdo a como se indica en esta guía de longitud, Fig. 3.

4. Conecte el sensor.

Tuerza conjuntamente los cables existentes en la caja de conexiones con los cables

del sensor RW600B utilizando los conectores (“wire nuts”) provistos de acuerdo al

diagrama Fig. 4.

• Conecte el cable verde (o alambre de cobre sin aislante) que conecta a TIERRA al

Cable verde del RW600B. Asegúrese que la tierra este bien conectada.

• Conecte el cable de LINEA (o FASE) del circuito al cable negro del RW600B.
• Conecte el cable que alimenta la lámpara o ventilador (CARGA) al cable rojo del

RW600B.

Tierra

LINEA/FASE (proveniente de la

caja de disyuntores o

“breakers”)

CARGA

(alimentación de

corriente

a la carga)

NEUTRO

Fig 2: Cableado típico

de un Circuito

Strip Gage

1/2"

12.7mm

Fig 3: Pelado apropiado

del cable

ADVERTENCIA

Desconecte la corriente que alimenta la caja de conexiones

apagando el disyuntor (breaker) o removiendo el fusible para

el circuito correspondiente antes de instalar el RW600B,

reemplazar luces,o realizar cualquier trabajo eléctrico.