WIRING INSTRUCTIONS

1. Disconnect power to the circuit by turning the circuit

breaker OFF before installation.

WARNING

TURN THE POWER OFF AT THE CIRCUIT

BREAKER BEFORE INSTALLING THE DIMMER.

2. Strip existing wire ½” (12.7mm).
3. Wire the LINE (black), NEUTRAL (white) and LOAD lead

wires to the supply/load wires per Figure 2. If installing

in a grounded metal box, the unit will be grounded to

the electrical box. Otherwise, use the green ground

screw to connect to ground as shown in Figure 2. Use

#12AWG copper wire. Depending on the application and

the number of connections, more space may be needed.

If so, use an appropriate size box or box extension.

4. If the MR2000 will be controlled by a wired multilocation

controller (MCD68/DCD68) connect the yellow traveler

wire per the instructions provided with the controller.

If using the MR2000 in a Miro wireless network, the

yellow traveler wire is not used and must be capped.

5. Switch the circuit breaker back ON.
6. If the unit is to be controlled from a Miro wireless

device, refer to “SET HOUSE ID” on the next page.

INSTALL IN COMPLIANCE WITH ALL APPLICABLE CODES

& STANDARDS. Failure to follow these instructions may

cause personal injury or equipment damage.

Load

Wires

Supply

Wires

Multilocation

Controller

Traveler (YEL)
Ground
Neutral (WHT)
Line

(BLK)

Load (RED)

Wire Legend

GND
(Connect
to
building
ground)

Max. traveler wire 200' (60m)

GND

Figure 2 - Wiring Diagram
A Miro 2000W Dimmer is compatible with wired Miro

devices, as shown above connected by a traveler wire

between the MR2000 and the Multilocation Controller (either

MCD68 or DCD68). It will also communicate with a wireless

Miro network (see Figure 1).

INSTALLATION

The unit must be installed in compliance with the

Environment and Orientation instructions.

CAUTION

Disconnect power when servicing fixture

or changing lamps. Both lighting fixture

and dimmer must be grounded. Use

this device only with copper wire.

Radio communication cannot be guaranteed if the unit is

mounted in a metallic electrical enclosure.
1. Install dimmer in a 21/

8

” minimum deep 4” square (1900)

electrical box with a 1½” extension. Extension must

extend beyond wall such that the heatsink is spaced a

minimum of 1½” from the wall.

2. For both wall and plenum mounting, orient the dimmer

so that the heat sink fins run vertically, allowing natural

upward convection.

3. Allow a minimum of 6” space above and below the unit

and do not block vertical airflow through the heat sink.

Requires 100 BTU/hour ventilation.

Figure 3 - Mounting Diagram

OPERATION

• When you see in the instructions, press the top

button on the MR2000, or the top of the paddle when

referencing other Miro devices.

• When you see in the instructions, press the bottom

button on the MR2000, or the bottom of the paddle when

referencing other Miro devices.

• When you see in the instructions, simultaneously

press and hold BOTH the UP and the DOWN buttons on

the MR2000 (or, when referencing other Miro devices,

firmly press and hold BOTH the top and bottom of the

device paddle).

DIMMER & PLATE

1 tap = last used level
2 taps = full output
Press and hold = raise light

level

1 tap = fade to OFF
Press and hold = reduces

light level

Figure 4: