Legrand DS4000 Mounting Bracket User Manual
Page 3
CABLE
CATEGORY/
O.D.
40% FILL 1/2
40% FILL w/DOWNWARD
TYPE
DESIGNATION
Inches
[mm]
COMPARTMENT
ACTIVATION/CROSSOVER
UNSHIELDED
4-pair, 24 AWG Cat 3
0.190
[4.8]
70
28
TWISTED PAIR
4-pair, 24 AWG Cat 5e
0.210
[5.3]
57
23
4-pair, 24 AWG Cat 6
0.250
[6.3]
40
16
4-pair, 24 AWG Cat 6a*
0.354
[9.0]
20
8
25-pair, 24 AWG
0.410
[10.4]
15
6
COAXIAL
RG6/U
0.270
[6.9]
35
14
FIBER
ZipCord
0.118 x 0.236
[3 x 6]
72
29
Round 4 Strand Fiber
0.187
[4.8]
73
29
Round 6 Strand Fiber
0.256
[6.5]
38
15
*Category 6 Augmented cable for 10 gigabit ethernet – max allowed cable diameter per Addendum 11 to ANSI/TIA-568-B.2.
DS4000 Raceway Wire Fill Capacities for Communication
WIRE SIZE
O.D.
DS4010A*
DS4011
DS4015
DS4017**
DS4018**
DS4075
DS4075A**
THHN
Inches
[mm]
40% 60%
40%
60%
40%
60%
40%
60%
40%
60%
40%
60%
40%
60%
THHN
14
0.111
[2.8]
125
187
171
256
62
93
160
239
142
213
106
160 142
213
12
0.130
[3.3]
91
137
125
187
45
68
116
175
104
156
78
116 104
156
10
0.164
[4.2]
57
86
78
118
28
43
73
110
65
98
49
73
65
98
8
0.216
[5.5]
33
50
45
68
16
25
42
63
38
57
28
42
38
57
6
0.254
[6.5]
24
36
33
49
12
18
31
46
27
41
20
31
27
41
UTP
2-pair, 24 AWG
0.150
[4.8]
68
103
94
140
49
74
87
131
78
117
58
87
78
117
4-pair, 24 AWG Cat 3
0.190
[4.8]
43
64
58
87
31
46
55
82
49
73
36
55
49
73
4-pair, 24 AWG Cat 5e
0.210
[5.3]
35
52
48
72
25
38
45
67
40
60
30
45
40
60
4-pair, 24 AWG Cat 6
0.250
[6.3]
25
37
34
51
18
27
32
47
28
42
21
32
28
42
4-pair, 24 AWG Cat 6a*
0.354
[9.0]
12
18
17
25
9
13
16
24
14
21
10
16
14
21
25-pair, 24 AWG
0.410
[10.4]
12
18
16
24
9
13
15
23
14
20
10
15
14
20
Coaxial RG6/U
0.270
[6.9]
21
32
29
43
15
23
27
41
24
36
18
27
24
36
Fiber
ZipCord
0.118 x 0.236 [3 x 6]
44
65
59
89
31
47
56
83
50
74
37
56
50
74
Round 4 Strand Fiber
0.187
[4.8]
44
66
60
90
32
48
56
85
50
75
38
56
50
75
Round 6 Strand Fiber
0.256
[6.5]
24
35
32
48
17
26
30
45
27
40
20
30
27
40
* Entrance end fitting fill rate is calculated using backfeed capability and radius inserts. Inserts are removable and fitting can obtain maximum
raceway fill from utilizing end fitting knockouts and removing radius control inserts.
**Calculated using radius control inserts. Inserts are factory installed and may be removed in order to obtain full raceway capacity if radius control
is not required.
DS4000 Raceway Fittings Wire Fill Capacity Chart
NOTE: For additional information, refer to the Technical Section of the current version of ED439 (Wiremold Buyer’s Guide).
NUMBER OF CONDUCTORS (40% FILL)
w/DUPLEX
w/SURGE GFCI
w/LARGE SINGLE
40% FILL
WIRE SIZE
O.D.
WITHOUT
RECT. DEVICES
DEVICES
RECEPTACLE
w/DOWNWARD
THHN/THWN
Inches
[mm]
DEVICES
1.59in.
2
[1025mm
2
]
2.30in.
2
[1485mm
2
]
3.00in.
2
[1935mm
2
]
ACTIVATION/CROSSOVER
14 AWG
0.111
[2.8]
206
141
111
83
46
12 AWG
0.130
[3.3]
150
103
81
60
33
10 AWG
0.164
[4.2]
95
64
51
38
21
8 AWG
0.216
[5.5]
54
37
29
22
12
6 AWG
0.254
[6.5]
39
27
21
15
8
DS4000 Raceway Wire Fill Capacities for Power