beautypg.com

Legrand Wallduct Medical Raceway System Bodies User Manual

Page 6

background image

Step 2 Drill four holes with a diameter of 9/32" [7.144mm]

to match with ceiling drop out mounting holes.
This can be best achieved by placing the drop
out onto duct body and marking with a marker
or pencil. These are the locations for the palnut
clips and machine screws.

Step 3 With cutout and holes made, place drop

out unit into body from top and screw into
place with palnut clips and #10-32 machine
screws. This installation is similar to that
of a coverplate.

Step 4 Adjust depth of drop out by loosening and

tightening the four #10-32 taptite screws on the
side of the unit until it sits flush as desired. Cut
desired hole size into drop out coverplate. Place
grommet supplied around field cut hole.

SPECIFIC INSTRUCTIONS: CEILING DROP OUT UNITS

Ceiling drop outs are intended for use with 10" [254mm] wide wallduct. The primary purpose is to allow wallduct
to sit flush with ceiling. Grommet all sharp edges to prevent wires from being damaged.

Step 1 With desired location selected, cut a hole

into bottom side (center) of duct body 8.75"
[222.25mm] wide and 8.75" [222.25mm] long.

NOTE: File all sharp edges and burrs on the wallduct that may cut

wire insulation.