beautypg.com

Legrand ALDS4000 Designer Series Large Raceway User Manual

Page 4

background image

4

CABLE

CATEGORY/

O.D.

40% FILL 1/2

40% FILL w/DOWNWARD

TYPE

DESIGNATION

Inches

[mm]

COMPARTMENT

ACTIVATION/CROSSOVER

UNSHIELDED

4-pair, 24 AWG Cat 3

0.190

[4.8]

70

28

TWISTED PAIR

4-pair, 24 AWG Cat 5e

0.210

[5.3]

57

23

4-pair, 24 AWG Cat 6

0.250

[6.3]

40

16

4-pair, 24 AWG Cat 6a*

0.354

[9.0]

20

8

25-pair, 24 AWG

0.410

[10.4]

15

6

COAXIAL

RG6/U

0.270

[6.9]

35

14

FIBER

ZipCord

0.118 x 0.236

[3 x 6]

72

29

Round 4 Strand Fiber

0.187

[4.8]

73

29

Round 6 Strand Fiber

0.256

[6.5]

38

15

*Category 6 Augmented cable for 10 gigabit ethernet – max allowed cable diameter per Addendum 11 to ANSI/TIA-568-B.2.

NOTE: For additional information, refer to the Technical Section of the current version of ED439 (Wiremold Buyer’s Guide).

DS4000 Raceway Wire Fill Capacities for Communication

NUMBER OF CONDUCTORS (40% FILL)

w/DUPLEX

w/SURGE GFCI

w/LARGE SINGLE

40% FILL

WIRE SIZE

O.D.

WITHOUT

RECT. DEVICES

DEVICES

RECEPTACLE

w/DOWNWARD

THHN/THWN

Inches

[mm]

DEVICES

1.59in.

2

[1025mm

2

]

2.30in.

2

[1485mm

2

]

3.00in.

2

[1935mm

2

]

ACTIVATION/CROSSOVER

14 AWG

0.111

[2.8]

206

141

111

83

46

12 AWG

0.130

[3.3]

150

103

81

60

33

10 AWG

0.164

[4.2]

95

64

51

38

21

8 AWG

0.216

[5.5]

54

37

29

22

12

6 AWG

0.254

[6.5]

39

27

21

15

8

DS4000 Raceway Wire Fill Capacities for Power

WIRE SIZE

O.D.

DS4010A*

DS4011

DS4015

DS4017**

DS4018**

DS4075

DS4075A**

THHN

Inches

[mm]

40% 60%

40%

60%

40%

60%

40%

60%

40%

60%

40%

60%

40%

60%

THHN

14

0.111

[2.8]

125

187

171

256

62

93

160

239

142

213

106

160 142

213

12

0.130

[3.3]

91

137

125

187

45

68

116

175

104

156

78

116 104

156

10

0.164

[4.2]

57

86

78

118

28

43

73

110

65

98

49

73

65

98

8

0.216

[5.5]

33

50

45

68

16

25

42

63

38

57

28

42

38

57

6

0.254

[6.5]

24

36

33

49

12

18

31

46

27

41

20

31

27

41

UTP

2-pair, 24 AWG

0.150

[4.8]

68

103

94

140

49

74

87

131

78

117

58

87

78

117

4-pair, 24 AWG Cat 3

0.190

[4.8]

43

64

58

87

31

46

55

82

49

73

36

55

49

73

4-pair, 24 AWG Cat 5e

0.210

[5.3]

35

52

48

72

25

38

45

67

40

60

30

45

40

60

4-pair, 24 AWG Cat 6

0.250

[6.3]

25

37

34

51

18

27

32

47

28

42

21

32

28

42

4-pair, 24 AWG Cat 6a*

0.354

[9.0]

12

18

17

25

9

13

16

24

14

21

10

16

14

21

25-pair, 24 AWG

0.410

[10.4]

12

18

16

24

9

13

15

23

14

20

10

15

14

20

Coaxial RG6/U

0.270

[6.9]

21

32

29

43

15

23

27

41

24

36

18

27

24

36

Fiber

ZipCord

0.118 x 0.236 [3 x 6]

44

65

59

89

31

47

56

83

50

74

37

56

50

74

Round 4 Strand Fiber

0.187

[4.8]

44

66

60

90

32

48

56

85

50

75

38

56

50

75

Round 6 Strand Fiber

0.256

[6.5]

24

35

32

48

17

26

30

45

27

40

20

30

27

40

* Entrance end fitting fill rate is calculated using backfeed capability and radius inserts. Inserts are removable and fitting can obtain maximum

raceway fill from utilizing end fitting knockouts and removing radius control inserts.

**Calculated using radius control inserts. Inserts are factory installed and may be removed in order to obtain full raceway capacity if radius control

is not required.

DS4000 Raceway Fittings Wire Fill Capacity Chart