PRESET INSERT INSTALLATION DETAILS

To Field Installed Presets:

1.

Be certain correct preset height is selected.

2.

Position preset so that hooks on bottom of preset drop into openings on duct.

3.

Push down evenly and slide forward. Knockout tab should snap into opening.

To Remove Mudcap:

1.

Strike a 1/4" flat blade screwdriver along the side of the mudcap to deflect the top edge.

2.

Use a screwdriver to pry out mudcap.

To Install Alignment Plates:

1.

Install plates at first set of presets on each length of duct before securing supports and couplings.

2.

All presets must be aligned within 1/8" [3.2mm].

S

P

PRESET

CUBIC

SYSTEM

PRESET

CATALOG

INCHES

DEPTH

HEIGHT

NUMBER

VOLUME

2 1/4"

[57mm]

7/8"

[22.2mm]

419-1

13.7

2 3/4"

[70mm]

1 3/8"

[34.0mm]

419-11/2

22.6

3 1/4"

[83mm]

1 7/8"

[47.0mm]

419-2

31.2

3 3/4"

[95mm]

2 3/8"

[61.0mm]

419-21/2

39.8

4 1/4"

[73mm]

2 7/8"

[73.0mm]

419-3

48.3

S

P

PRESET

CUBIC

SYSTEM

PRESET

CATALOG

INCHES

DEPTH

HEIGHT

NUMBER

VOLUME

2 1/2"

[64mm]

7/8"

[22.2mm]

419-1

13.7

3"

[76mm]

1 3/8"

[34.0mm]

419-11/2

22.6

3 1/2"

[89mm]

1 7/8"

[47.0mm]

419-2

31.2

4" [102mm]

2 3/8"

[61.0mm]

419-21/2

39.8

4 1/2" [115mm]

2 7/8"

[73.0mm]

419-3

48.3

#2 DUCT SYSTEMS ONLY

#4 DUCT SYSTEMS ONLY

Galvanized Steel
Mudcap

Pry Out Here

Die Cast Preset
(See Chart)

NOTE: Three Duct Systems are Similar.

Alignment Plate

3.3 Sq. In.

8.5 Sq. In.

P

S

1 1/2"

[38mm]

1/8" [3.2mm] Concrete over Preset

1 11/16"

[43mm]

Galvanized Steel
Mudcap

Pry Out Here

Die Cast Preset
(See Chart)

NOTE: Important!

Tighten Bonding

Screw when Preset

is activated.

3.3 Sq. In.

1/8" [3.2mm] Concrete over Preset

P

S

1 1/4"

[32mm]

Add 1/4" [6.4mm] to System when
using both #2 and #4 Duct.

Minimum 1 1/2" [38mm] Concrete
required below duct or solid surface.