Wire Size

No. of Wires

THHN/THWN

O.D.

@ 40% Fill

Power Wiring

10 AWG

0.153

15

Without Devices

12 AWG

0.122

31

14 AWG

0.105

45

Power Wiring

10 AWG

0.153

With Plugmold Devices

12 AWG

0.122

8*

14 AWG

0.105

8*

*Includes the four conductors of the wiring harness.

Lay out Raceway path. Determine feed method and location
from figures A, B, and C below.

1

Measure and cut raceway base and cover.
See commmon fittings dimensions below.

2

Install raceway and fittings bases
using No. 8 flathead screws.

3

Install wire in raceway and install wire clips as needed.

Install blank
end fittings with
No. 8 flathead
screws where
needed. Slide
raceway cover
into end fitting.

A1

A2

Field Wired Raceway – NM2000 Series:

A

Snap on raceway and fitting covers.

A3

Wiring Method – Refer to Instructions (A thru E) according to your application.

Fig. A* – Back Feed

Fig. B – End Feed

Fig. C – Feed from Existing Wall Box

1 3/4"

[45mm]

1 5/8" [41mm]

from edge of wall

1" [25mm]
from edge

of wall

1 1/16"
[27mm]

* This method is not recommended if splice area is less

than 4". See Figure B or C for feeding this condition.

NM2051H

NM2010A

NM2000WC

NM2010B

Base

PLUGMOLD PLUS

NM2000

I N S T A L L A T I O N I N S T R U C T I O N S

Installation Instruction No.: 41080R4 – Updated June 2003

Wiremold Electrical Systems conform to and should be installed
and properly grounded in compliance with requirements of the
current National Electrical Code, Canadian Electrical Code or
codes administered by local authorities.

All electrical products may represent possible shock or fire hazard
if improperly installed or used. Wiremold electrical products are
UL Listed to U.S. and Canadian safety standards,made for interior
use only, and should be installed in conformance with current local
and/or the National Electrical Code.