Pass & Seymour Network Wiring:
Two Category 5e inserts provided with Cat. Nos. RC4A and RC4C,
other modules shown not included, sold separately.
NOTE: To accommodate both Keystone and Avaya jacks, four communication inserts are provided with every unit (two dual port Keystone jack inserts, 2A-U2KEY-BK,
and two dual port Avaya jack inserts, 2A-U2ATT-BK). Two Activate Dual Category 5e (2A245-B5-BK) inserts are also included. Whichever option is not installed
may be discarded.
Step 11. Insert blanking plugs or neoprene foam blocks in unused communication ports.
CAUTION: Empty communication ports must be closed off
with foam blocks or TracJack blanks to maintain
fire classification.
Communication inserts may be mounted either flush or
recessed. Some inserts, such as fiber optic, must be
mounted recessed in order for slides to close properly.
Instructions for mounting communication inserts are
shown in Step 10.
Step 12. Place gasket support plate
Step 13. Align gasket over
Step 14. Attach slide cover with
on Poke-Thru inserting the
receptacles and press
two #6-32 screws.
four posts through holes
bead into flange channel.
on receptacle brackets.
CAUTION: Gasket must be set in place
to provide scrub water seal.
RC4 Poke-Thru Less Junction Box Assemblies Only
Cat. Nos. RC4ATC-LJB, RC4ARTTC-LJB, RC4ATCLJB25
and RC4ARTTCLJB25.
(Applies to installations in the City of Chicago or other locations where
local codes require the use of a communication adapter, EMT compression
fittings, and a junction box suitable for use in environmental air spaces.)
Step 15. Follow steps 1 - 14 for installation.
Step 16. Installation complete.
Both Recessed
Recessed/Flush
Both Flush
TracJack Blank (Supplied)
Foam Plug (Supplied)
TracJack Sold Separately
Communication Jack
Sold Separately
Attach COM75
Adapter (Included
with LJB Units)
Per Instructions
Supplied with Unit
Once Poke-Thru is Pushed into the
Cored Hole, from Below, Install a EMT
Compression Fitting (Not Supplied) and
Junction Box (Not Supplied) to the
Conduit System. Complete Installation
Per NEC and Local Codes.