Legrand RC3 Receptacle Replacement User Manual
Page 2
2
WHITE or NEUTRAL
from branch circuit
WHITE
from poke-thru receptacle
BLACK or HOT
from branch circuit
BLACK
from poke-thru receptacle
GREEN (jumper wire)
from poke- thru junction box
GREEN
from poke-thru receptacle
CONVENTIONAL WIRING SCHEMATIC
WHITE or NEUTRAL
from branch circuit
WHITE
from poke-thru receptacle
BLACK or HOT
from branch circuit
BLACK
from poke-thru receptacle
GREEN (jumper wire)
from poke-thru junction box
ISOLATED GROUND
from branch circuit
GREEN
from poke-thru receptacle
ISOLATED GROUND WIRING SCHEMATIC
GREEN or GROUND
from branch circuit
SYSTEM GROUND
GREEN or GROUND
from branch circuit
SYSTEM GROUND
WARNING:
Ground wire from junction box must be connected to SYSTEM GROUND.
Step 5 Snap new receptacle into trim flange.
Step 6 Replace gasket and slide holder with the two #6-32
screws provided.
CAUTION:
Make sure bosses on receptacle match
up with cutout in the trim flange.
CAUTION:
Gasket must be set in place to provide
a scrub water seal.
CAUTION:
Receptacle mounting means not
grounded. Grounding wire connection
required. For isolated ground wiring,
connect ground leads to a separate
isolated grounding conductor.
See NEC250-146(d).
NOTE: Factory supplied junction box shown. Junction boxes
must be located in an accessible location. Poke-Thru
devices with an “LJB” or “LJB25” suffix are supplied
without a junction box (supplied by others).
CAUTION:
Do not over tighten cover mounting screws.
Step 7 Wire up connections in the junction box. Connect
poke-thru conductors according to required device
configuration. See schematic below.
Cat. No. RC37REC
or RC37REC-25