beautypg.com

Legrand AV3 User Manual

Page 2

background image

CONVENTIONAL WIRING SCHEMATIC

ISOLATED GROUND WIRING SCHEMATIC

BLACK or HOT

BLACK

BLACK or HOT

BLACK

From branch circuit

from Poke-Thru receptacle From branch circuit

from Poke-Thru receptacle

WHITE or NEUTRAL WHITE

WHITE or NEUTRAL WHITE

From branch circuit

from Poke-Thru receptacle From branch circuit

from Poke-Thru receptacle

GREEN or GROUND GREEN

ISOLATED GROUND GREEN

From branch circuit

from Poke-Thru receptacle From branch circuit

from Poke-Thru receptacle

System Ground

GREEN or GROUND GREEN

(jumper wire)

From branch circuit

from Poke-Thru

System Ground

junction box

GREEN (jumper wire)
from Poke-Thru
junction box

WARNING: Ground wire from junction box must be connected to system ground.

2

Slide Cover
Mounting Screws
Two (2) #6-32

Outlet Box

Cover Plate Screw

Complete Assembly:

Step 6

Wire the Poke-Thru device. (Can be
completed above floor.) Refer to
wiring schematic in Step 8.

Step 7

Wire the POWER and Communications
circuits. (See Steps 10 & 11 for
Communication Selection)

CAUTION: Poke-Thru can not be rotated in hole after

inserted into the floor.

NOTE: Electrical and communication

cables may be connected to unit
prior to or after activation.

NOTE: Factory supplied junction box shown. Junction

boxes must be located in an accessible location.
Poke-Thru devices with an "LJB" or "LJB25"
suffix are supplied without a junction box (sup-
plied by others).

CAUTION: Receptacle mounting means not grounded. Grounding

wire connection required. For isolated ground wiring,
connect ground leads to a separate isolated
grounding conductor. See NEC 250-146(d).

NOTE: The orange triangle shall only be placed on

devices that are wired for isolated ground.
See NEC 250-146(d).

Step 8

Connect Poke-Thru conductors according
to required device configuration. See
schematic below.

Step 9

If circuit is connected to an isolated ground,
apply IG icon on receptacle slide as shown.