Legrand AMD8 Communications Poke-Thru Device User Manual
Amd8 poke-thru series, Installation instructions
Products Covered: AMD8STC, AMD8ATC, AMD8ARTTC, AMD8CTC, AMD8CRTTC, AMD8SHTC.
CAUTION: DO NOT operate tile stripper or resurfacing equipment over top of covers. This may result in damage to the
surface finish of the product.
Suitable for use in air handling spaces in accordance with Sec. 300-22 (C) of the National Electrical Code.
AMD8 Poke-Thru Series
INSTALLATION INSTRUCTIONS
Installation Instruction No.: 1 003 912 – April 2004
Walker
®
electrical systems conform to and should be properly grounded
in compliance with requirements of the current National Electrical Code
or codes administered by local authorities.
All electrical products may present a possible shock or fire hazard if
improperly installed or used. Walker electrical products may bear the
mark as UL Listed and/or Classified and should be installed in
conformance with current local and/or the National Electrical Code.
24" [610mm] Min
Center – Center
7"
[178mm] Diameter
CAUTION: Be certain to drill hole at least 4" [102mm] from
any wall or pillar to leave enough room for
Poke-Thru cover assembly.
CAUTION: For tile installations up to a maximum of
3/4" [19.1mm] thick.
NOTE: For tile thickness greater than 3/4" [19.1mm]
consult factory.
IMPORTANT: Please read all instructions
before beginning.
CAUTION: Spacing is limited to no more than one hole per each
65 sq. ft. [6 sq. m] of floor area in each span.
Step 2
Remove 7" diameter [178mm] section from
carpet or tile. Use template provided.
Step 1 Layout and locate position of hole(s).
Step 3 Core drill hole.
CAUTION: Poke-Thru cannot be rotated in
hole after insertion into floor.
4" [102mm] Diameter Core Drill
4 1/16" [103mm] Actual Diameter
Push Down
#6-32 x 1/4" FHMS
three (3) required
Step 4 Stem Assembly:
Catalog No. AMD8STC
Insert stem into hole.
Step 5
Cover Assembly:
Catalog No. AMD8CTC.
Remove disposable plate
and replace with carpet/tile
flange. Install with three (3)
#6-32 x 1/4" [6.4mm] FHMS.