Legrand RFB Series Floor Boxes User Manual
Rfb series floor boxes
RFB Series Floor Boxes
I N S T A L L A T I O N I N S T R U C T I O N S
Installation Instruction No.: 1 007 256R2 – Updated January 2012
Legrand/Wiremold electrical systems conform to and should be properly
grounded in compliance with requirements of the current National
Electrical Code or codes administered by local authorities.
All electrical products may present a possible shock or fire
hazard if improperly installed or used. Legrand/Wiremold electrical
products may bear the mark as UL Listed and/or Classified and
should be installed in conformance with current local and/or the
National Electrical Code.
IMPORTANT: Please read all instructions
before beginning.
BEFORE CONCRETE POUR:
Step 1. Determine box location and conduit layout.
Step 2. Take off box top by removing two (2) #8-32 screws
attaching cover to base.
Step 3. Remove necessary knockouts. Attach conduit and
fittings (not supplied by Wiremold) to steel base.
Step 4. Configure adjacent compartments.
RFB4E Series Boxes are configured with solid removable
partitions that can be discarded for wire pass through.
Replace #8 screw back into base after barrier removal.
RFB Series Floor Boxes and Activations are UL Listed for use with tile, terrazzo and carpet covered concrete floors.
RFB6 and RFB6-OG Floor Boxes and Activations are also UL Listed for use with floors of wood construction.
PRODUCTS: Floor Box Cat. Nos.: RFB4E, RFB4E-OG, RFB6, RFB6-OG, RFB6E, RFB6E-OG
Device Plate Cat. Nos.: RFB6B, RFB6DP, RFB6GFI, RFB6S1, RFB6S2, RFB6RT, RFB6EXT,
RFB62A, RFB6-AAP
Furniture Feed Kit Cat. Nos.: RFB4KIT, RFB6KIT
Bare Concrete & Terrazzo Ring Cat. Nos.: RFB4E-CTR, RFB6E-CTR
(2) #8-32 Screws
Remove KOs & attach
Fittings and Conduit
RFB4E – Remove and discard
Barrier for pass through
Replace #8 Screw after
removing Barrier
RFB6 & RFB6E – Remove Plug and replace
with Bushing as required for pass through
Step 5. Re-attach box cover to base with two (2) #8-32 screws
removed during Step 2.
RFB6 and RFB6E Series Boxes are configured with
non-removable partitions containing pre-installed
plugs. Depending on wiring configuration, plugs may
be replaced with included bushings for wire pass
through. This may be done pre- or post-pour.