Legrand CRFB Series Floor Box User Manual

Crfb series floor box

background image

CRFB Series Floor Box

I N S T A L L A T I O N I N S T R U C T I O N S

Installation Instruction No.: 1 009 621 – September 2010

Legrand/Wiremold electrical systems conform to and should be properly
grounded in compliance with requirements of the current National
Electrical Code or codes administered by local authorities.

All electrical products may present a possible shock or fire
hazard if improperly installed or used. Legrand/Wiremold electrical
products may bear the mark of a Nationally Recognized Testing
Laboratory (NRTL) and should be installed in conformance with current
local and/or the National Electrical Code.

IMPORTANT: Please read all instructions

before beginning.

1. Prior to installation, an 8-3/8 ± 1/8 in. [213 ± 3 mm]

diameter hole must be cut or preformed into the raised
floor panel or wood floor. If knockouts on sides of box
are to be used, proceed to steps 4 and 5. Pull cable and
conduit through opening prior to termination.

2. If necessary, use bushing(s) and wire tunnel to facilitate

wire and cable routing. Remove the temporary cover and
the (5) #8 hex screws securing the device mounting plate
and lift it out of the box, exposing the internal barriers.
Remove necessary knockouts and twistouts between
compartments to allow desired wiring layout. Replace the
internal barriers and reinstall the device mounting plate
back in its original orientation.

3. Attach flexible conduit and fittings to the steel box body.

Terminate wiring devices in compliance with the NEC
and local codes. Cover each compartment with the
Device Plate that matches both the Location and Type
of Device used.

PRODUCTS COVERED: CRFB4, CRFBBTC, CRFBCTC, CRFB-X-1, CRFB-X-2, CRFB-X-3 AND CRFB-X-4.
Also 8ATC and 8CT Covers when installed on CRFB Series Floor Boxes.

8 3/8" ± 1/8"
[213 ± 3mm]

Temporary

Cover

#8 Hex

Screw

Bushing

Right

Barrier

Device Mounting

Plate

Center Barrier

(with KO removed)

Left

Barrier

Wire

Tunnel

Device

Location #1

Device

Location #3

Device

Location #4

Device

Location #2

NOTE:

Floor thickness range (including floor
covering 3/8" – 2" [9.5mm – 51mm].