Legrand FS User Manual
Page 5
![background image](https://www.manualsdir.com/files/794330/content/doc005.png)
5
A.
B.
A.
FS2RWP8, FS4RWP12 WALL PLATE INSTALLATION:
Add-On Kit used to retrofit Flamestopper Thru-Wall Fitting over holes in the wall cables already installed. Use FS2RWP8 –
8" trade size Wall Covering Plate with FS2R. Use FS2RWP12 – 12" trade size Wall Covering Plate with FS4R.
1.
4.
B. Tighten Screw.
3.
Use Insulation as template for holes.
2.
Measure Wall thickness.
CAT NO.
MAX. HOLE AREA
FS2RWP8
36 IN
2
FS4RWP12
100 IN
2
Wall
Thickness
Cut Split Sleeve to length. Wall
thickness plus 2 3/4" [70mm].