Legrand FS User Manual
Flamestopper, Fs2r, fs4r installation – thru-wall & thru-floor
![background image](https://www.manualsdir.com/files/794330/content/doc001.png)
FlameStopper
™
Thru-Wall & Thru-Floor Fittings
INSTALLATION INSTRUCTIONS
Installation Instruction No.: INS0010R2 – Updated January 2007
Wiremold / Legrand Electrical Systems conform to and should be
installed and properly grounded in compliance with
requirements of the current National Electrical Code, Canadian
Electrical Code or codes administered by local authorities.
All electrical products may represent possible shock or fire
hazard if improperly installed or used. Wiremold / Legrand
electrical products are UL Listed to U.S. and Canadian
safety standards, made for interior use only, and should
be installed in conformance with current local building codes
and/ or the National Electrical Code.
1. Determine location and drill
pilot hole thru wall or floor.
Drill hole using 4 3/4"
[120mm] for FS4R and
2 1/4" [58mm] for FS2R.
NOTE: Use core drill when going
through concrete or
block walls or floors.
2. Measure wall or floor thickness.
Cut EMT Sleeve to length.
3. Peel off backing
for adhesive.
1. Insert EMT
into Box.
Wall or Floor Thickness
Wall or Floor Thickness
+ 1 5/8" [41mm]
4. Stick on Wall or floor (Make
sure wall or floor is clean
and dust-free).
NOTE: Do not force EMT through
intumescent material.
NOTE: Do not over tighten.
2. Tighten Clamp.
5. Install cabling then adjust
sliding doors to be snug
around cables by turning
side screws.
4.
Products Covered: FS2R, FS4R, FS2RHS, FS4RHS, FS2RWP8, FS4RWP12
6. Ground in accordance with
National Electrical Codes.
7. Fill out and place
label on wall or floor
near FlameStopper.
Minimum Spacing
CAT NO.
MINIMUM SPACING
FS4R
6 1/8"
[155MM]
FS2R
3 7/8"
[98MM]
FS2R, FS4R INSTALLATION – Thru-Wall & Thru-Floor:
3.
1. Peel off backing
for adhesive.
2. Stick on Wall
or floor.
3. Tighten Clamp.