Wiremold electrical systems conform to and should be properly
grounded in compliance with requirements of the current National
Electrical Code or codes administered by local authorities.

All electrical products may present a possible shock or fire
hazard if improperly installed or used. Wiremold electrical products
may bear the mark as UL Listed and/or Classified and should
be installed in conformance with current local and/or the National
Electrical Code.

Products Covered: 8ATCP, 8ATP, 8ATC, 8AT, 8STC, 8CTC, 8CT, 68REC, 68MAAP, 682A, 68B, 8DP, 8DEC, 8S1, 8S2,

8MAAP, 8AAP, 8B, 8TS, 8STCP, 575CHA, 575PTHA, 575BLH, 175CHA, 1125CHA, 1PTHA, 1BLH, 22CHA, CE8STCP

CAUTION: DO NOT operate tile stripper, cleaning, or resurfacing equipment over top of covers. This may result in

damage to the surface finish of the product.

Suitable for use in air handling spaces in accordance with Sec. 300-22 (C) of the National Electrical Code.

Evolution

Series

8" Poke-Thru Devices

I N S T A L L A T I O N I N S T R U C T I O N S

Installation Instruction No.: 1 007 156 R2 – Updated May 2010

CAUTION: Be certain to locate hole at least 8" [203mm] from any wall or

pillar to leave enough room for Poke-Thru cover assembly.

IMPORTANT: Please read all instructions

before beginning.

CAUTION: Minimum spacing of 2ft on center and not more than

one device per each 65 square feet of floor area in
each span.

Step 2

Remove 8 1/2" dia. [216mm] section from
carpet or tile. Use template provided.

Step 1 Layout and locate position of hole(s).

FLOOR PREPARATIONS

24" [610mm] Min
Center – Center

8 1/2"

[216mm]

Covered Floors

8"

[203mm]

8 1/8"

[206mm]

(Carpet, Tile or
Wood)

Bare Concrete

8 1/16" [205mm]

8 1/8"

[266mm]

or Terrazzo

FLOOR

CORE

CORE

TYPE

SIZE (Min.)

SIZE (Max.)

Step 3 Create core hole according to the

dimensions provided in the chart.