Installation evaporative cooler piping (optional), Important, Caution – Greenheck TSU Base Unit Manual (464441) User Manual
Page 9: Install the water supply line, Install the drain line, Check/adjust water level

Make-Up Air Unit
9
®
Auto Drain & Flush Valves
(when provided by Manufacturer)
Assm.
Number
Mfg.
Part
Number
ASCO
Part Num-
ber
Solenoid
Type
De-Energized
Position
Diameter
Qty.
852178
461262
8210G2
Supply
Closed
1/2 inch
(12.7 mm)
1
461263
8262G262
Supply
Line
Drain
Open
1/4 inch
(6.35 mm)
1
461264
8210G35
Sump
Drain
Open
3/4 inch
(19.05 mm)
1
Part numbers subject to change.
IMPORTANT
The supply line should be of adequate size and 
pressure to resupply the amount of water lost due to 
bleed-off and evaporation. The drain line should be 
the same size or larger than the supply line.
CAUTION
All solenoid valves and traps must be installed 
below the roof to protect the supply water line from 
freezing. If they cannot be installed below the roof, an 
alternative method must be used to protect the lines 
from freezing.
IMPORTANT
The supply solenoid (Valve A) is NOT the same as the 
drain solenoids (Valve B and Valve C). Make sure to 
use the proper solenoid for each location. Check your 
local code requirements for proper installation of this 
type of system.
1. Install the Water Supply Line
Supply line opening requirements vary by unit size 
and arrangement and are field-supplied. Connect the 
water supply line to the float valve through the supply 
line opening in the evaporative cooling unit. Install the 
1/2 in. normally closed solenoid (Valve A) in the supply 
line. Install the 1/4 in. normally open solenoid (Valve B) 
between the supply line and the drain line. Refer to Auto 
Drain and Fill Evaporative Piping drawing shown on this 
page.
2. Install the Drain Line
Connect an unobstructed drain line to the sump drain 
overflow connection. Install the 3/4 in. normally open 
solenoid (Valve C) between the sump drain connection 
and the drain line.
A trap should be 
used to prevent 
water from 
overflowing the 
sump pump. Refer to 
drain trap diagram.
3. Check/Adjust Water Level
Check the water level in the sump tank. The water 
level should be above the pump intake and below the 
overflow. Adjust the float and drain pipe as needed to 
achieve the proper water level.
6 in. min.
6 in. min.
Drain
Trap
Auto Drain and Fill Evaporative Piping
Installation Evaporative Cooler 
Piping (optional) 
continued
Evaporative Cooling with Auto Drain and Fill
Sump Overflow
Trap
Drain Line
Sump Drain
Supply Line
VALVE A
Supply Solenoid
(normally closed)
VALVE C
Sump Drain Solenoid
(normally open)
VALVE B
Supply Line Drain Solenoid
(normally open)
