Make-Up Air Unit

14

®

6. Set the Maximum Firing Rate

Monitor the unit’s actual temperature rise by placing
a thermocouple in the unit’s inlet and a second in the
discharge, three duct diameters downstream of the
burner.

Send the unit to maximum fire by disconnecting and
isolating the wire connected to Terminal 3 on the
Maxitrol 14 or 44. On Maxitrol SC 25 system, place
jumper between T1 and T2 on the amplifier.

While monitoring the unit’s temperature rise, set the
maximum firing rate by adjusting the regulator until the
designed temperature rise is achieved. After setting the
maximum firing rate, reconnect the wire to the amplifier.

NOTE

The low fire time delay must be set high enough to
provide at least 10 seconds of low fire while the unit
tries to light.

“ W.C.

“ W.C.

“ W.C.

F

PSI

“ W.C.

“ W.C.

MAX BTU/HR

BTU/H MAX

NORMAL MANIFOLD

PRESSURE

PRESSION D’ADMISSION

NORMALE

MIN GAS

PRESSURE

PRESSION DE GAZ

MIN BURNER

PRESSURE DROP

PERTE MIN DE PRESSION

DANS LE BRULEUR

TYPE OF GAS

NATURE DU GAZ

MIN BTU/HR

BTU/H MIN

MIN GAS PRESSURE

FOR MAX OUTPUT

PRESSION DE GAZ MIN

POUR PUISSANCE MAX

MAX BURNER

PRESSURE DROP

PERTE MAX DE PRESSION

DANS LE BRULEUR

MAX GAS

PRESSURE

PRESSION DE GAZ

MAX

DESIGN ΔT
Δ

T NORMALE

EQUIPPED FOR

CONCU POUR

SCFM

“ W.C.

EXTERNAL STATIC PRESSURE

PRESSION STATIQUE EXTERIEURE

AGAINST

CONTE

NOTE

Do not set the burner maximum firing rate based on
gas pressure. It should be set based on the unit’s
designed temperature rise shown on the direct gas
label.

NOTE

Clockwise rotation increases the temperature rise,
counterclockwise rotation decreases the temperature
rise.

NOTE

The minimum setting for the maximum firing rate may
be higher than required. This is acceptable, the burner
will modulate as needed.

Direct Gas Nameplate

Regulators and Modulating Valves

Remove cap to access

maximum firing rate

adjustment

Remove one wire to

send the unit to the
minimum firing rate

Separate Regulator and Modulating Valves

Minimum firing

rate adjustment

Combined Modulating Regulator

Maximum firing

rate adjustment

Remove one wire to send the unit

to the minimum firing rate

Minimum firing

rate adjustment

7. Set the Minimum Firing Rate

Disconnect and isolate one of the wires running to the
modulating valve to send the unit to its minimum firing
rate. Set the minimum firing rate by adjusting the needle
valve.

After setting the minimum firing rate, shut off the pilot
to ensure that the flame safeguard can still read the
main flame signal. Reconnect the wire to the modulation
valve and open the pilot shut-off valve.

IMPORTANT

Setting the maximum firing rate during mild weather
conditions may cause the high limit to trip out during
extreme conditions requiring manual resetting.

NOTE

Gas trains are equipped with either separate
regulators and modulating valves or with a combined
modulating valve.

5. Set the Low Fire Time Delay

Set the low fire time delay to 75% of its maximum
setting. See corresponding image(s) for the location of
the time delay setting.