Troubleshooting, Blower does not operate – Greenheck TSU Base Unit Manual (464441) User Manual

Page 22

background image

Make-Up Air Unit

22

®

Proper supply power at

main disconnect

Check Main Voltage

(See Blower Start-Up – Step 1)

Main Disconnect (DS1) Off

(Turn Main Disconnect DS1 On)

Primary Fuses Blown

(Replace Fuses)

24 VAC between

terminals R and X?

Main Transformer (TR1) Tripped

(Reset Transformer)

Main Transformer (TR1) Defective

(Replace Transformer)

24 VAC between

terminals G and X?

Supply Switch (S2) Off

(Turn Supply Switch (S2) On)

Fire system contact (FSC) tripped/not installed

(Correct/Replace)

No

No

No

No

No

No

Yes

Yes

Yes

Yes

Yes

Yes

Blower Does Not Operate

Broken Fan Belt

(Replace - reference V-Belt Drives in the Maintenance section)

Defective motor or capacitor

(Repair/Replace)

Blown Motor Fuse

(Replace)

One or more legs of 3 phase is out

(Restore missing legs)

24 VAC across A2 and A1 on

supply contactor (ST1)

24 VAC across

terminals 4 and X?

24 VAC across

terminals 2 and X?

Supply Fan Overload (ST1 OL) Tripped

(Reset and check motor amps, reference Blower Start-Up – Step 4)

Optional Exhaust Fan Interlocks (ST2-ST5) Open

(Correct/Replace)

(Optional) Damper Limit Switch (DL1) Holding

(Wait for actuator to open fully or adjust limit switch)

(Optional) Damper Limit Switch Jumper Missing

(Install jumper, reference the unit’s ladder diagram for terminals)

Fan Relay (RF) is not energized

(Check for loose connection) (Repair or replace relay)

(Optional) Freeze Protection (RT4) Tripped

(Cycle Power and Reset)

Troubleshooting

At this time the supply contactor (ST1) should

pull in, passing power to the supply motor

and the blower should start.