Troubleshooting, Heater does not operate – Greenheck TSU Base Unit Manual (464441) User Manual
Page 26

Make-Up Air Unit
26
®
Heater Does Not Operate
Does not attempt to light (No visible spark)
Troubleshooting
24 VAC between
terminals W1 and X?
Heat Switch (S4) Off
(Turn Heat Switch (S4) On)
Heat Switch Not Wired
(Wire Heat Switch (S4))
115 VAC between
terminals 102 and 101?
Primary Fuses Blown
(Replace Fuses)
Main Transformer (TR4) Defective
(Replace Transformer)
115 VAC between
terminals 106 and 101?
(Optional) High/Low Gas Pressure Switch(es)
(PS3 and PS4) Tripped
(Correct gas pressure and reset)
(Reference Direct Gas Start-Up – Steps 2 and 3)
115 VAC between
terminals 104 and 101?
High Limit (HLC1) Tripped
(Reset/Replace High Limit (HLC1))
(Check cause of high limit trip)
115 VAC between
terminals 107 and 101?
115 VAC between
terminals 103 and 101?
(Optional) Inlet Air Sensor (TS4) Holding
(Adjust TS4 setting. Reference Blower Start-Up – Step 6)
Heat Relay (RH) Defective
(Replace Heat Relay (RH))
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Flame safeguard detective.
Yes
The power light on the flame safeguard should
blink approximately every 5 seconds as it
performs a self-diagnostics check.
At this time the heater should attempt to light.
(The pilot light on the flame safeguard should illuminate).
115 VAC between
terminals 108 and 101?
Airflow Switch (PS2) Holding for Proper Airflow
(Correct airflow across burner)
(Reference Direct Gas Start-Up - Step 4)
No
Yes