beautypg.com

Troubleshooting, Insufficient airflow, Too much airflow – Greenheck TSU Base Unit Manual (464441) User Manual

Page 24

background image

Make-Up Air Unit

24

®

Insufficient Airflow

Troubleshooting

Damper(s) not fully opened?

Adjust damper linkage(s), or replace faulty actuator(s).

(Damper actuators may take a few minutes to open)

Filters dirty or clogged?

Clean or replace filters.

(Reference Filters in the Maintenance section).

Blower speed too low?

Adjust drives as needed.

(Reference Blower Start-Up – Step 5)

System static losses too high?

Reduce losses by improving ductwork.

Yes

Yes

Yes

Yes

No

No

No

No

No

Leaks in ductwork?

Repair leaks.

Yes

Belt slipping?

Replace or tighten belt.

(Reference V-Belt Drives in the Maintenance section)

Yes

Everything is working properly,

consult factory.

Yes

Too Much Airflow

Blower speed too high?

Adjust drives as needed.

(Reference Blower Start-Up – Step 5)

Insufficient external static

pressure?

Increase external static pressure.

Filters not in place?

Install filters.

Yes

Yes

Yes

No

No

Everything is working properly,

consult factory.

No