Make-Up Air Unit

18

®

NOTE

The Freeze Temperature is preset to the factory
recommended 45ºF. Steps 9-11 should only
be completed if the Freeze Temperature needs
adjustment.

NOTE

The Freeze Temperature is the temperature at which
the supply solenoid closes and the drain solenoid
opens to drain the supply line, preventing possible
freeze damage. A drain solenoid is required for this
option.

9. Enter Program Mode

Press and hold the
Enter key for three

seconds. The display will
read “Pro” when Program
Mode is active.

10. Adjust the Freeze Temperature

While in Program
Mode, use the Up and
Down keys to navigate
through the Menu
Options until “Frt”
is displayed. Press

the Enter key to access the
selected Menu Option setting.

Use the Up and Down keys to adjust the Freeze
Temperature setting as needed. Press the Enter key to
set the Freeze Temperature and return to the Program
Menu.

Freeze Temperature

Display

NOTE

The enter key must be pressed to save the new freeze
temperature.

Program Mode

Program Mode allows the user to view the Program
Menu and edit the factory default settings. To access
Program Mode and view the Program Menu, press and
hold the Enter key for three seconds. While viewing the
Program Menu, press the Up and Down keys to scroll
through the Menu Options. To view the setting of the
selected Menu Option, press the Enter key. To edit the
setting, press the Up or Down key while viewing the
setting. To save the setting and return to the Program
Menu, press the Enter key. To return to the Program
Menu without saving the change, wait 10 seconds.
To exit Program Mode from the Program Menu, wait
10 seconds.

Operation - Water Wizard™ (optional)

CAUTION

The sump drain line must be clear and draining to a
safe location before using Flow Test Mode.

CAUTION

Be aware of the water level in the sump tank at all
times when using the Flow Test Mode.

WARNING

Changing the default settings will significantly affect
performance. Only change a setting after reading and
understanding this entire manual.

WARNING

The Enter key must be pressed to save any changes
made to a setting.

Light Status

Indicating

Light

On

Off

Blinking

Long on, short off

Blinking

Short on, long off

L1

Call for
cooling

No

call for

cooling

Call for cooling.

Outdoor

temperature

lockout.

N/A

L2

Drain

solenoid

open

Drain

solenoid

closed

N/A

Supply solenoid

open. (Drain

solenoid closed).

L3

Cooling

on

Cooling

off

Supply solenoid

locked closed

Flow test

mode active

Drain Mode locks open the drain solenoid and drains
the supply line between the supply solenoid and
the media. To activate Drain Mode simultaneously,
press the Function and Enter keys (L2 will light). To
deactivate Drain Mode and unlock the drain solenoid,
simultaneously press the Function and Enter keys again.

Flow Test Mode - Activating Flow Test Mode opens
the supply solenoid and allows water to pass to the
manual supply valve. To activate Flow Test Mode, press
and hold the Function key for one second (L3 will flash).
To deactivate Flow Test Mode and allow the supply
solenoid to close, press and hold the Function key again
for one second.

Dry Bulb Temperature

The dry bulb temperature is visible on the home screen.
If a number is not visible, wait 15 seconds and use the
Up and Down keys until a number is displayed.

Wet Bulb Temperature

To view the Wet Bulb Temperature, simultaneously press
and hold the Up and Down keys.

Indicating Lights

Three indicating lights are located across the top of the
display to indicate the status of the Water Wizard™.

11. Exit Program Mode

After ten seconds of idle time the controller will exit
Program Mode.

Program Display