beautypg.com

Troubleshooting, Motor overamps – Greenheck TSU Base Unit Manual (464441) User Manual

Page 23

background image

Make-Up Air Unit

23

®

Motor Overamps

Troubleshooting

Air volume too high?

Adjust drives or increase external

static pressure as needed.

(Reference Blower Start-Up – Step 5)

Motor horsepower too low?

Resize motor.

Motor voltage correct?

Provide proper power supply.

(Reference Blower Start-Up – Step 1)

Blower rotation correct?

Reverse blower rotation.

(Reference Blower Start-Up – Step 2)

Actual static pressure

lower than design?

Adjust drives to reduce blower RPM.

(Reference Blower Start-Up – Step 5)

No

No

Yes

Yes

Yes

Yes

No

Yes

No

No

Shorted windings in motor?

Replace motor.

Yes

Everything is working

properly, consult factory.

No