beautypg.com

Check operation - vav units (optional), Modulating, Variable volume operation – Greenheck TSU Base Unit Manual (464441) User Manual

Page 19: Burner bypass damper (optional), Warning

background image

Make-Up Air Unit

19

®

WARNING

The burner bypass damper is set-up at the factory.
The weights should not be adjusted in the field. The
damper may not fully close during minimum outside
air mode.

NOTE

Blower Start-Up, Steps 1-5 should be performed
before the blower is run.

NOTE

For maintenance issues associated with variable
frequency drives, consult the drive’s manual supplied
with the unit. The drives are programmed at the
factory and should not need any adjustment during
installation and start-up. For kitchen applications, the
drive may be located in the kitchen or in the unit.

Modulating

Potentiometer Control - a variable frequency drive
is controlled by input from a remote
speed selector (potentiometer). This
unit allows easy manual adjustment
of make-up air volumes. To test
potentiometer operation, turn the
potentiometer to the two extremes.
With variable volume, make sure the
fan goes to maximum and minimum
speed.

When the potentiometer is at 0, the
fan speed will be at its minimum.
When the potentiometer is at 100,
the fan will be at its maximum speed.

Variable Volume Operation

The variable volume option is recommended when
a building’s exhaust volume may vary. This option
enables the make-up air volume to track with the
exhaust volume, providing only the amount of make-up
air required. Control strategies include 2-speed VFD
motors and modulating blowers. Before the unit is left in
service, the variable volume control system should be
tested.

EXHAUST

(OPTIONAL)

(OPTIONAL)

55

60

65

70

75

80

85

90

SUPPLY

HEAT

DIRTY FILTERS

MAIN VALVES

BLOWERS

Potentiometer

Control

Check Operation - VAV Units
(optional)

Building Pressure Control - a
variable frequency drive is controlled
according to input from a pressure
sensing device.

Turn both knobs to the upper most
pressure setting. You may have to
remove the outdoor pressure tap
tubing. VAV systems should go to
maximum speed. Set both knobs
at the lowest setting and the VAV
systems should go to minimum speed.

Reset the correct pressure limits
before starting the unit.

This picture depicts a typical
photohelic setting. The needle
indicates a negative building
pressure. During correct
operation, the indicating
needle will remain between or
near the setting needles.

External Signal - a variable
frequency drive is controlled
according to input from an
external 2-10 VDC or 4-20 mA
signal (by others).

A 2 VDC or 4 mA signal will send the blower to low
speed. The blower will go to maximum speed with a 10
VDC or 20 mA signal.

Variable Kitchen Control - a variable frequency drive
is controlled by input from the kitchen control panel.
This unit allows automatic adjustment of make-up air
volumes based on varying cooking loads.

Burner Bypass Damper (optional)

The self-adjusting burner bypass damper is a device
used in variable volume
units. Its function is
to maintain proper
combustion by providing
a constant airflow over
the burner when outside
air volumes are changed.
It is located underneath
the burner as shown in
the picture.

70

65

75

80

85

90

60

55

(OPTIONAL)

BLOWER

DIRTY FIL TERS

MAIN V AL VES

EXHAUST

SUPPL Y

HEA T

(OPTIONAL)

PHOTOHELIC

Building

Pressure Control

Photohelic Gauge

Pressure

Indicating

Needle

Pressure

Setting

Needles

Pressure Setting Knobs

Burner Bypass Damper

Burner

Bypass Damper