Check Operation - Recirculating
Units (optional)

NOTE

Blower Start-Up, Steps 1-5 should be performed
before the blower is run.

Recirculation Operation

The recirculation operation option is recommended
when the ventilation equipment provides the primary
source of heating for the space. A minimum of 20%
outdoor air is mixed with up to 80% recirculated air.
Control strategies include 2-position and modulating
dampers. Before the unit is left in service, the
recirculation control system should be tested.

2-Position Damper

A 2-position spring return actuator is used to control
the return air amounts. The damper
moves from open to closed. If
power is cut to the unit, the outdoor
air damper will fail to the closed
position.

Turn the recirculating switch on
the remote control panel to each
position and confirm that the return
air damper adjusts accordingly. The
damper actuator may take a few
minutes to open or close.

Modulating

Potentiometer Control - a modulating spring return
actuator is used to control the return air amounts. The
return air damper modulates from fully open to fully
closed based on a signal from a
remote potentiometer.

To test potentiometer operation,
turn the potentiometer to the two
extremes. With 80/20 recirculation,
confirm that the return air damper
fully opens and fully closes. When
the potentiometer is at 0, the return
air damper will close. When the
potentiometer is at 100, the return
air damper will open. The damper
actuator may take a few minutes to
open or close.

70

65

75

80

85

90

60

55

(OPTIONAL)

BLOWER

DIRTY FIL TERS

MAIN V AL VES

RECIRCULA TION

EXHAUST

SUPPL Y

HEA T

(OPTIONAL)

2-Position

Damper Control

EXHAUST

(OPTIONAL)

(OPTIONAL)

55

60

65

70

75

80

85

90

SUPPLY

HEAT

DIRTY FILTERS

MAIN VALVES

BLOWERS

Potentiometer

Control

Building Pressure Control - a floating point spring
return actuator is used to control
the return air amounts. The return
air damper modulates from fully
open to fully closed based on a
signal from a remote pressure
sensing device.

Turn both knobs to the upper most
pressure setting. You may have
to remove the outdoor pressure
tap tubing. The return air damper
should close.

Set both knobs at the lowest
setting and the damper should
open. It may take one to two
minutes for the damper to
reach the desired position.

Reset the correct pressure
limits before starting the unit.

This picture shows a typical
photohelic setting. The needle
in this photo indicates a
negative building pressure.
During correct operation, the
indicating needle will remain
between or near the setting
needles.

External Signal - a modulating spring return actuator
is used to control the return air amounts. Return air
damper modulates from fully open to fully closed based
on an external 2-10 VDC or 4-20 mA signal (by others).

The return air damper will open with a 10 VDC or 20 mA
signal. The return air damper will close with a 2 VDC
or 4mA signal. The damper actuator may take a few
minutes to open or close.

70

65

75

80

85

90

60

55

(OPTIONAL)

BLOWER

DIRTY FIL TERS

MAIN V AL VES

EXHAUST

SUPPL Y

HEA T

(OPTIONAL)

PHOTOHELIC

Building Pressure

Control

Photohelic Gauge

Pressure

Indicating

Needle

Pressure

Setting

Needles

Pressure Setting Knobs