Issues, observation, and suggestions – Gasboy TopKAT PLUS Bypass Switch Installation User Manual
Page 6

Issues, Observation, and Suggestions
Gasboy
®
is a registered trademark of Gasboy International. Orpak
™
is a trademark of Orpak Systems Ltd. TopKAT
™
is a trademark of
Gasboy International.
© 2013 GASBOY
7300 West Friendly Avenue · Post Office Box 22087
Greensboro, North Carolina 27420
Phone 1-800-444-5529 ·
· Printed in the U.S.A.
MDE-5073 TopKAT™ PLUS Bypass Switch Installation Instructions · March 2013
Issues, Observation, and Suggestions
Following observation and suggestions have been made from reviewing the documentation
and field installation drawings from Orpak
™
for the optional Manual Override feature for the
TopKAT PLUS mechanical system.
Issues
Observation
Suggestions
Override/Bypass Switch is
recommended and shown to be
located in the circuit breaker/sub
panel.
Due to location and distance of the circuit
breaker panel, and the requirement to run
the AC and DC in two separate conduits.
It is not suggested or recommended to
have low voltage DC around or near high
voltage AC of the circuit breaker panel
which may/will place noise on the low
voltage line that may/will effect the
operation of the bypass feature not to
function properly.
• Place the Bypass Switch in a secured
explosion/weather proof enclosure on or
near the TopKAT PLUS or fuel island
following the National Electrical Code
(NEC) regulations, 18-inch off the
ground and 18-inch from a pump. Two
conduits must run to the enclosure.
• For kiosk located on or near the fuel
island, suggested applications can be
installed and located in the pedestal,
above the 18-inch barrier plate of the
TopKAT PLUS.
The double pole switch contains
high AC voltage switch on one
pole and low DC voltage switch
on the other pole.