MDE-5073 TopKAT™ PLUS Bypass Switch Installation Instructions · March 2013

Page 5

Manual Override Feature

Manual Override Feature

The Bypass Switch is also connected to the MPI-C (low voltage DC), that triggers the proper
LED on the board and lets the system know that the pump was put in bypass and also triggers
the proper alarm in the controller.

Event Viewer will show an event of pump switched to bypass (with relevant pump number).
Controller will show yellow triangle over the pump and communication error will be created.
Also, device status will show the relevant pump disconnected.

Manual Override Test - Optional

On completion of the system wiring, the pumps and/or dispensers must be tested to verify if
the AC wiring is correct. Following steps indicate the proper procedure for testing and the
expecting results. If any of these tests fail, the wiring must be corrected and the test must be
performed again.

1

Place all the override switches in OFF position.

2

Turn on the breakers for all the pumps/dispensers and system.

3

Locate the override switch(s) and place the override switch for hose 1 in the Manual (up)
position.

4

Turn on hose 1. After completing reset, the hose must be able to dispense the product.

5

Turn on all other hoses. No other hoses besides 1 must activate.

6

Turn off all hoses.

7

Place the override switch for hose 1 in OFF position.

8

Repeat steps

3

to

7

for all remaining hoses.