Removal and Installation Instructions

Page 4

MDE-4527 Gasboy Cold Weather External Filter Field Upgrade Kit • October 2005

Removal and Installation Instructions

TOP VIEW

TOP VIEW

1

2

3

Nipple extends
past side panel

or

Parts In Kit

Item No.

Part Number

Qty.

Description

1

025903

1

Filter Adapter 2” CIM-TEK 420 (revision D or later)

2

025900

2

Filter Element CIM-TEK 800-10 (standard)

3

025901

2

Filter Element CIM-TEK HS10 (hydro)

not shown

M06450B001

2

Filter Gasket (cold weather fluorosilicone) CIM-TEK 90546

1

Ensure power to unit has been removed and locked out.

2

Release any residual pressure through the hose nozzle into an approved container.

3

Place approved catch pan and absorbent material to catch any fuel.

4

Wearing safety goggles, carefully remove existing filter adapter. Save piping for reuse.

5

Remove and discard black gaskets that come with come with the filters.

6

Install new filter adapter (P/N 025903, rev D or later) onto piping using UL approved gas and
oil resistant pipe compound on male threads only.

Note: Placing pipe compound on female threads can force compound into piping and possibly

cause a malfunction of the equipment.

7

Install filter elements (PN/ 0259000 or P/N 0259001) using the blue fluorosilicone gaskets
(M06450B001) in the kit.