Removal and installation instructions, Parts in kit – Gasboy Cold Weather External Filter Upgrade Kit User Manual
Page 4

Removal and Installation Instructions
Page 4
MDE-4527 Gasboy Cold Weather External Filter Field Upgrade Kit • October 2005
Removal and Installation Instructions
TOP VIEW
TOP VIEW
1
2
3
Nipple extends
past side panel
or
Parts In Kit
Item No.
Part Number
Qty.
Description
1
025903
1
Filter Adapter 2” CIM-TEK 420 (revision D or later)
2
025900
2
Filter Element CIM-TEK 800-10 (standard)
3
025901
2
Filter Element CIM-TEK HS10 (hydro)
not shown
M06450B001
2
Filter Gasket (cold weather fluorosilicone) CIM-TEK 90546
1
Ensure power to unit has been removed and locked out.
2
Release any residual pressure through the hose nozzle into an approved container.
3
Place approved catch pan and absorbent material to catch any fuel.
4
Wearing safety goggles, carefully remove existing filter adapter. Save piping for reuse.
5
Remove and discard black gaskets that come with come with the filters.
6
Install new filter adapter (P/N 025903, rev D or later) onto piping using UL approved gas and
oil resistant pipe compound on male threads only.
Note: Placing pipe compound on female threads can force compound into piping and possibly
cause a malfunction of the equipment.
7
Install filter elements (PN/ 0259000 or P/N 0259001) using the blue fluorosilicone gaskets
(M06450B001) in the kit.