beautypg.com

Changing default control mode, 2 changing default control mode – Bronkhorst EL-FLOW Prestige User Manual

Page 45

background image

Bronkhorst High-Tech B.V.

EL-FLOW Prestige

45

9.17.084

alternative pulse length must be specified on order.

Provide a pull-up resistor of 5...10 kOhm to create 15...24 Vdc at pin 5 according to the hook-up diagram

document 9.16.118.

Example for -F9B- hook-up

H1E

4…20 mA input, external sensor

Sensor input, this function disables the internal sensor.

I3C

Digital input, controller mode valve close

Valve closes when pin 5 is connected to 0 Vdc.

This function switches between the default ‘

12

Control Mode’ and mode (‘Valve Close’) (value 3). When the default

12

Control Mode’ is ‘digital’ the default value is 0 (‘BUS/RS232’ mode), when the default ‘

12

Control Mode’ is

‘analog the default value is 1 (‘Analog Input’ mode).

I8C

Digital input, controller mode valve purge

Valve is fully opened when pin 5 is connected to 0 Vdc.

This function switches between the default ‘

12

Control Mode’ and mode (‘Valve Fully Open’) (value 8). When the

default ‘

12

Control Mode’ is ‘digital’ the default value is 0 (‘BUS/RS232’ mode), when the default ‘

12

Control Mode’

is ‘analog' the default value is 1 (‘Analog Input’ mode).

I1R

Digital input, reset counter

The counter resets when pin 5 is connected to 0 Vdc.

Example for -I1R- or -I2R- hook-up

I2R

Digital input, reset alarm

The alarm resets when pin 5 is connected to 0 Vdc.

4.4.2

Changing default control mode

Instruments are factory-set with the control mode set for either analog or digital setpoint source. See parameter ‘

12

Control Mode’

to change the control mode. However after every (power-up) reset the instrument will return to its default control mode. To

change the control mode permanently use the following procedure:

Changing default digital operation to default analog operation:

1. Set parameter ‘

7

Init Reset’ to 64

2. Read parameter ‘

86

IOStatus’

3. Add 64 to the read value

4. Write the new value to parameter ‘

86

IOStatus’

5. Set parameter ‘

7

Init Reset’ to 82

Changing default analog operation to default digital operation:

1. Set parameter ‘

7

Init Reset’ to 64

2. Read parameter ‘

86

IOStatus’

3. Subtract 64 from the read value