Other field bus configurations
The following field buses are optionally available for the EL-FLOW Prestige instruments. For all mentioned field bus systems the EL-
FLOW Prestige instruments serve as slaves on the master/slave bus system. There is no mutual communication between slaves,
only between master and slave.
PROFIBUS DP
PROFIBUS DP is a 2-wire, RS485-based industrial data communication standard (field bus) which allows automation components
(like sensors, actuators and controllers) to exchange information. For more information regarding the PROFIBUS DP interface refer
to document 9.17.025.
DeviceNet
TM
The DeviceNet
TM
interface offers direct connection to a DeviceNet
TM
network according to the Mass Flow Controller Profile
specified by the ODVA. The Bronkhorst DeviceNet
TM
instrument is a Group 2 Only Server device which messages comply with the
Controlled Area Network (CAN) 2.0A standard and with the DeviceNet
TM
protocol. See document 9.17.026 for more information
about the DeviceNet
TM
interface.
EtherCAT®
Ethernet for Control Automation Technology (EtherCAT
®
) is an open high performance Ethernet-based field bus
system. The
EtherCAT® interface is described in more detail in document 9.17.063.
PROFINET
The PROFINET interface is 100% Ethernet-compatible and is used for data exchange between IO controllers (PLC, etc.)
and IO devices (slaves, field devices). PROFINET uses the proven communication model and application view of
PROFIBUS DP.
Refer to document 9.17.095 for more information.
3.6.1
Hook-up
See the following documents for hook-up diagrams and instructions for setting up bus communication with the following
communication interfaces:
PROFIBUS DP interface: hook-up diagram 9.16.121 and manual 9.17.025
DeviceNet
TM
interface: hook-up diagram 9.16.122 and manual 9.17.026
EtherCAT® interface: hook-up diagram 9.16.124 and manual 9.17.063
PROFINET interface: hook-up diagram 9.16.147 and manual 9.17.095
3.6.2
Baud rate, node address and parity setup
In the table below for the supported configurations for PROFIBUS DP, DeviceNet
TM
, EtherCAT® and PROFINET are shown. The
default selections are presented in bold.
Mode:
Digital
Connector:
9-pin D-sub (female)
5-pin M12 (male)
2x RJ45 (in/out)
2x RJ45
Interface/medium:
RS485
RS485
Ethernet
Ethernet
Protocol:
PROFIBUS DP
DeviceNet
TM
EtherCAT®
PROFINET
Baud rate:
Autodetect
(9600)
(19200)
(45450)
(93750)
(187500)
(500000)
(1500000)
(3000000)
(6000000)
(12000000)
125000
250000
500000
100000000
100000000
Node address:
0…126
0...63
0 (n/a)
0 (n/a)
Parity:
Even
None
None
None
PROFIBUS DP, DeviceNet
TM
, EtherCAT® and PROFINET communication options