Bronkhorst EL-FLOW Prestige User Manual
Page 40
![background image](https://www.manualsdir.com/files/776608/content/doc040.png)
Bronkhorst High-Tech B.V.
EL-FLOW Prestige
9.17.084
40
Alarm Delay Time
Type
Access
Range
FlowDDE
FLOW-BUS
Modbus
Unsigned char
RW
0…255
182
97/7
0x0C27/3112
This value represents the time in seconds the alarm action will be delayed when an alarm limit has been exceeded. This value also
delays the alarm off action if an alarm limit is no longer exceeded. Default value = '0'.
Alarm Maximum Limit
Type
Access
Range
FlowDDE
FLOW-BUS
Modbus
Unsigned int
RW
0…32000
116
97/1
0x0C21/3106
Maximum limit for the ‘
8
Measured Value’ to trigger the maximum alarm situation (after ‘
182
Alarm Delay Time’). Range 0…32000
represents 0…100% signal. The ‘
116
Alarm Maximum Limit’ value must be greater than the ‘
117
Alarm Minimum Limit’ value. Default
value = '0'.
Alarm Minimum Limit
Type
Access
Range
FlowDDE
FLOW-BUS
Modbus
Unsigned int
RW
0…32000
117
97/2
0x0X22/3107
Minimum limit for the ‘
8
Measured Value’ to trigger the minimum alarm situation (after ‘
182
Alarm Delay Time’). Range 0…32000
represents 0…100% signal. The ‘
117
Alarm Minimum Limit’ value must be smaller than the ‘
118
Alarm Maximum Limit’ value. Default
value = '0'.
Alarm Setpoint Mode
Type
Access
Range
FlowDDE
FLOW-BUS
Modbus
Unsigned char
RW
0…1
120
97/5
0x0C25/3110
Value 0: No setpoint change at alarm (default)
Value 1: New setpoint at alarm enabled (set at value ‘
121
Alarm New Setpoint’)
Alarm New Setpoint
Type
Access
Range
FlowDDE
FLOW-BUS
Modbus
Unsigned int
RW
0…32000
121
97/6
0x0C26/3111
New (safe) setpoint during an alarm until reset. Range 0…32000 represents 0…100% setpoint. Default value = '0'.
Reset Alarm Enable
Type
Access
Range
FlowDDE
FLOW-BUS
Modbus
Unsigned char
RW
0…15
156
97/9
0C029/3114
Available alarm reset options (convert value to binary number to see which bits are active):
Bit
Low (0)
High (1)
Description
0
Off
On
Reset by micro switch
1
Off
On
External reset (not used)
2
Off
On
Reset by parameter ‘Reset’
3
Off
On
Automatic reset (when alarm conditions no longer apply)
Alarm reset options
Default value: value 15, all conditions above are enabled.