Report template (rpt), Metering parameters – Basler Electric BE1-851 Modbus Protocol User Manual
Page 61

9289900992 Rev F
BE1-851 Modbus
™ Protocol
3-23
47525-26
Fault
Clearing
Time
FP
Read only:
0 if Fault Clearing Time Status is not 0 (not valid).
Time (xxx.xxx) in seconds if Fault Clearing Time Status is 0 (valid).
47527
Fault Breaker Operate Time Status
SI
Read
only:
0 if Valid Fault Breaker Operate Time (Registers 47528-29) value
1
if
Unknown
2 if N/A; Out of range
3 if No operation
47528-29
Fault
Breaker
Operate
Time
FP
Read
only:
0 if Fault Breaker Operate Time Status is not 0 (not valid).
Time (xxx.xxx) in seconds if Fault Breaker Operate Time Status is 0 (valid).
47530-31
Fault Phase A Current Magnitude
FP
47533-34
Fault Phase B Current Magnitude
FP
47536-37
Fault Phase C Current Magnitude
FP
47539-40
Fault Residual Current Magnitude
FP
47542-43
Fault Neg-Seq. Current Magnitude
FP
Read only:
Value in amps
Report Template (RPT)
47595-719 Report
Text
Read only:
ASCII string (illegal message response generated for invalid Report Focus
value).
Metering Parameters
49720
Part Number
INT
Read
only:
0 to 999
49726-27
Phase
A
Current
Magnitude
FP
49729-30
Phase
B
Current
Magnitude
FP
49732-33
Phase
C
Current
Magnitude
FP
49735-36
Residual
Current
Magnitude
FP
49738-39
Neg-Seq
Current
Magnitude
FP
Read
only:
Value in amps
49835-54
Error
Details
ASC(40)
Read
only:
ASCII string
49875-999
Contiguous
Poll
Block
Mixed
Read only:
Mixed values