Logic mask and terms – Basler Electric BE1-851 Modbus Protocol User Manual
Page 40

3-2 BE1-851
Modbus
™ Protocol
9289900992 Rev F
4 for Oscillator
5 for Integrating
6 for Latch
42010
Programmable Settings Group Logic Mode
INT
Read
and
Write:
0 for all setting groups disabled except Group 0
1 for selecting setting group via pulsed input logic
2 for selecting setting group via sustained input logic
43173 Programmable
79
Logic
Mode
INT
Read
and
Write:
0 for Recloser disabled
1 for Recloser standard power-up operation
2 for Recloser power-up to close operation
43234
Programmable 262 Timer Logic Mode
∗
INT
43267
Programmable 362 Timer Logic Mode
∗
INT
Read
and
Write:
0 for disabled
1 for Pickup/Dropout
2 for One-Shot Non-Retriggerable
3 for One Shot Retriggerable
4 for Oscillator
5 for Integrating
6 for Latch
∗ 262 and 362 are available when style option 1 is V or W.
Logic Mask and Terms
Each set bit in the “mask” parameter indicates a significant variable in the equation. A corresponding bit in
the "term" parameter indicates that the variable must be TRUE / 1 if set or FALSE / 0 if not set.
Mask and Term - 1
st
Register (Logic Var 0 to 15)
BM(16)
Read only:
Bit 15 - 150TQ picked-up (350TN, Sensing input “G”)
Bit 14 - 50TQ picked-up (250TN, Sensing input “G”)
Bit 13 - 150TN picked-up
Bit 12 - 50TN picked-up
Bit 11 - 150TP picked-up
Bit 10 - 50TP picked-up
Bit 9 - 51Q tripped (151N, Sensing input “G”)
Bit 8 - 51N tripped
Bit 7 - 51P tripped
Bit 6 - BF tripped
Bit 5 - 150TQ tripped (350TN, Sensing input “G”)
Bit 4 - 50TQ tripped (250TN, Sensing input “G”)
Bit 3 - 150TN tripped
Bit 2 - 50TN tripped
Bit 1 - 150TP tripped
Bit 0 - 50TP tripped
Mask and Term - 2
nd
register (Logic Var 16 to 31)
BM(16)
Read only:
Bit 15 - Logic always false L-VOx=0
Bit 14 - 79 block output
Bit 13 - 79 reclose fail
Bit 12 - 79 lockout
Bit 11 - 79 enable / active / block tap changer
Bit 10 - 79 close
Bit 9 - Serial controlled switch 343 (Serial controlled switch 143
∗)