Global settings parameters – Basler Electric BE1-851 Modbus Protocol User Manual
Page 47

9289900992 Rev F
BE1-851 Modbus
™ Protocol
3-9
40283-84
150TP
Time
Delay
LI
40287-88
150TN
Time
Delay
LI
40291-92
150TQ Time Delay (350TN, Sensing input “G”)
LI
Read and Write:
0 to 60,000 milliseconds
40305-06
51P
Pickup
FP
40311-12
51N
Pickup
FP
40317-18
51Q Pickup (151N, Sensing input “G”)
FP
Read and Write:
0.50 to 16.00 amps (5A units)
40307-08
51P
Time
Dial
FP
40313-14
51N
Time
Dial
FP
40319-20
51Q Time Dial (151N, Sensing input “G”)
FP
Read and Write:
0.0 to 9.9
40309-10
51P
Curve
Type ASC(3)
40315-16
51N
Curve
Type ASC(3)
40321-22
51Q Curve Type (151N, Sensing input “G”)
ASC(3)
Read only: One of the following ASCII strings.
S1, S2, L1, L2, D, M, I1, I2, V1, V2, E1, E2, S1R, S2R, L1R, L2R, DR, MR, I1R,
I2R, V1R, V2R, E1R, E2R, A, B, C, G, F, P, AR, BR, CR, GR, FR, PR
40359-60
62
Time
Delay
1 LI
40361-62
62
Time
Delay
2 LI
40363-64
162
Time
Delay
1
LI
40365-66
162
Time
Delay
2
LI
40367-68
262 Time Delay 1
∗
LI
40369-70
262 Time Delay 2
∗
LI
40371-72
362 Time Delay 1
∗
LI
40373-74
362 Time Delay 2
∗
LI
Read and Write:
0 to 999,000 milliseconds
40406-07
79 First Automatic Reclose Delay
LI
40408-09
79 Second Automatic Reclose Delay
LI
40410-11
79 Third Automatic Reclose Delay
LI
40412-13
79 Fourth Automatic Reclose Delay
LI
40414-15
79
Reset
Time
Delay
LI
40416-17
79 Reclose Fail Time Delay
LI
40418-19
79
Maximum
Reclose
Time
LI
Read
and
Write:
100
to
600,000
milliseconds
40420
79
Sequence
Control
BM(16)
Read
and
Write:
Bit 0 to Block Shot #1
Bit 1 to Block Shot #2
Bit 2 to Block Shot #3
Bit 3 to Block Shot #4
Bit 4 to Block Shot #5
∗ 262 and 362 are available when style option 1 is V or W.
Global Settings Parameters
40606-07
Breaker
Fail
Time
Delay
LI
Read
and
Write:
100 to 999 milliseconds