Basler Electric BE1-851 Modbus Protocol User Manual
Page 56

3-18 BE1-851
Modbus
™ Protocol
9289900992 Rev F
47377
Current Output Control Settings (OutputLatch0) MSBs
BM(16)
Read
only:
Bits 15 to 6 - Spare
Bit 5 - Output 5 latch low
Bit 4 - Output 4 latch low
Bit 3 - Output 3 latch low
Bit 2 - Output 2 latch low
Bit 1 - Output 1 latch low
Bit 0 - Output A latch low
47378
Current Output Control Settings (OutputLatch1) LSBs
BM(16)
Read
only:
Bits 15 to 6 - Spare
Bit 5 - Output 5 latch high
Bit 4 - Output 4 latch high
Bit 3 - Output 3 latch high
Bit 2 - Output 2 latch high
Bit 1 - Output 1 latch high
Bit 0 - Output A latch high
47379
Current
Output
Contact
Status
BM(16)
Read
only:
Bits 15 to 6 - Spare
Bit 5 - Output 5
Bit 4 - Output 4
Bit 3 - Output 3
Bit 2 - Output 2
Bit 1 - Output 1
Bit 0 - Output A
47380
Active
Alarm
Flags
(SumFlags)
MSBs
BM(16)
Read
only:
Bits 15 to 0 - Spare
47381
Active
Alarm
Flags
(SumFlags)
LSBs
BM(16)
Read
only:
Bits 15 to 10 - Spare
Bit 9 - Calibration defaults loaded
Bit 8 - Setting defaults loaded
Bit 7 - Watchdog failure
Bit 6 - Power Supply error
Bit 5 - Calibration error
Bit 4 - Analog failure
Bit 3 - EEPROM Read / Write Fatal error
Bit 2 - MPU Self-test error
Bit 1 - ROM (flash) Failure detected
Bit 0 - RAM Failure detected
47382
Active
Alarm
Flags
(ProgAlarms)
MSBs
BM(16)
Read Only:
Bits 15 to 10 - Spare
Bit 9 - Changes Lost alarm
Bit 8 - Logic = None alarm
Bit 7 - Fault Record Time Out
Bit 6 - Virtual Output 15 alarm
Bit 5 - Virtual Output 14 alarm
Bit 4 - Virtual Output 13 alarm
Bit 3 - Setting Group Change Active alarm
Bit 2 - Loss of IRIG-B sync or IRIG-B decode problem
Bit 1 - An override is active in one or more outputs
Bit 0 - EEPROM Non fatal error