Register details, Introduction, Logic settings – Basler Electric BE1-851 Modbus Protocol User Manual
Page 39: Logic modes, Section 3, Register details -1

9289900992 Rev F
BE1-851 Modbus
™ Protocol
3-1
SECTION 3
• REGISTER DETAILS
INTRODUCTION
This section details the register formats and data ranges of the previous section. The two sections
combined provide all information necessary to communicate with the BE1-851 Modbus
™ Holding
Registers.
Any Holding Register not listed in the Register Table is an unassigned Holding Register. A value of zero
always results when reading an unassigned Holding Register. Writes to unassigned Holding Registers
are legal, but no action will be taken (the write is ignored).
Logic Settings
Logic settings consist of a combination of modes, masks, terms, and term counts. Logic modes are
specific to each logic set, while the masks, terms, and term counts have value definitions consistent
throughout all logic sets. A single logic equation consists of a “mask” and “term” pair. The logic “term
count” is used only in VOA, VO1 - VO15 virtual output logic blocks.
The logic “mode” enables or disables the logic equation for that logic block.
The logic “mask” corresponds to the System Status bits to be evaluated. These bits are referenced in the
desired logic equation and are set to 1 (non-used bits masked out as 0‘s).
The logic “term” corresponds to the System Status bit’s TRUE or FALSE state referenced in the desired
logic equation where only the TRUE bits in the equation are set to 1.
The logic “term count” may be of one of four logic types which are NONE (logic disabled), OR only (a + b
+ c), AND only (a
∗ b ∗ c) or MIXED (a ∗ b + b ∗ c).
The following defines all logic set parameters:
Logic Modes
41505
Programmable 50TP Block Logic Mode
INT
41522
Programmable 50TN Block Logic Mode
INT
41539
Programmable 50TQ Block Logic Mode (250TN, “G”)
INT
41556
Programmable 150TP Block Logic Mode
INT
41573
Programmable 150TN Block Logic Mode
INT
41590
Programmable 150TQ Block Logic Mode (350TN, “G”)
INT
Read
and
Write:
0
for
disabled
1
for
enabled
41658
Programmable Breaker Failure Logic Mode
INT
Read
and
Write:
0
for
disabled
1
for
enabled
41691
Programmable
51P
Logic
Mode
INT
41708
Programmable
51N
Logic
Mode
INT
41725
Programmable 51Q Logic Mode (151N, “G”)
INT
Read and Write:
0 for disabled
1 for enabled
41844
Programmable 62 Timer Logic Mode
INT
41877
Programmable 162 Timer Logic Mode
INT
Read and Write:
0 for disabled
1 for Pickup/Dropout
2 for One-Shot Non-Retriggerable
3 for One Shot Retriggerable